beautypg.com

ERICO LENTON INTERLOK Rebar Splicing System User Manual

Page 23

background image

17

www.erico.com

2.4 Gravity Fill Installation Instructions

For HY10L Filler Material

6) Mix the HY10L according to the mixing directions on the bag. Use only full bags of HY10L for each batch made.

7) Grout may be placed by hand or a grout pump may be used to place the HY10L. Contact ERICO for recommended grout

pumps. NOTE: Before using the grout pump, carefully read and understand the Pump Users Manual. It is important to follow

all the manufacturer’s recommended guidelines regarding safety, operations, service, and maintenance.

8) For gravity fill application, pump or pour the HY10L evenly and continuously into the open end of the coupler. Referring

to the table on the following page, fill the coupler to the level “A” shown for the bar size of interest measuring down

from the top with a ruler and filling the grout to that level. It is acceptable to slightly overfill the coupler, as any excess

grout will be removed when the bars are placed inside the coupler. However, for maximum grout economy it is advised

that the couplers be filled with the proper amounts to avoid waste.

!!CAUTION!! DO NOT UNDERFILL the coupler as this will result in reduced connection and performance. Coupler should be

filled completely and fully. Grout should be placed into the coupler in one step and no cold joints should be present.

9) Once the couplers have been filled to the proper level, remove any air that may be trapped in the HY10L by tamping it

with a small diameter rod.

10) Once the HY10L has been tamped, immediately lower the precast member until it is properly seated and aligned. It is

advised that the precast member be lowered slowly into the coupler to avoid air bubbles. Check to make sure the panels

are level and that grout completely surrounds the rebar to the top.
NOTE:

It is recommended that all grouting operations are inspected by the engineer to make sure that all the manufacturer’s

recommended procedures and all applicable building codes have been observed. If any HY10L leaks out onto the

surface of the precast panel remove it immediately with flushing water to avoid unsightly rust stains.

11) The decision to remove bracing following grouting must be determined solely by the Structural Engineer. In order to

ensure a quality structural connection, it is important that the grouted couplers in a precast panel or member be secured

and undisturbed by movement, shock, or vibration until the HY10L has reached a compressive strength of at least 3000

psi (21 MPa). Typically this will occur after 1 day at 68°F (20°C), however, this time will vary depending on the temperature

and job site conditions. In cold weather, the curing time will be significantly lengthened (2 or more days at 40°F; 4°C),

therefore, the bracing time may need to be increased. It is strongly recommended that the compressive strength of the

HY10L be checked under job site curing conditions according to the procedures outlined in ASTM C-109 before proceeding

with upper story erection.

12) Once the installation of the grout is complete and the panels are braced and secured, fill the seam between the two panels

with a dry pack sealing mortar.

!!CAUTION!!

ANY OF THE FOLLOWING ITEMS IF NOT OBSERVED MAY RESULT IN REDUCED CONNECTION PERFORMANCE.

1) Refer to Mixing Directions and Cautions on the LENTON

®

INTERLOK bag before mixing or doing any work with the

HY10L. Do not use any damaged, wet, or open bags. Do not use grout which is more than 1 year old. These bags

should be discarded in accordance with Federal, State, and Local Regulations.

2)

When pumping, never let the hopper become empty as this will result in air getting into the couplers.

Prepare additional HY10L to keep on hand to avoid this situation.

3) If grouting is interrupted, keep recirculating the HY10L by operating the pump with the nozzle in the hopper. This

movement of the HY10L will aid in keeping it fluid. If the shut down exceeds the limits of time specified in this manual

noted in Figure 1 of Hot & Cold Weather Grouting Instructions, (for example 60 minutes at 70°F (21°C), THE GROUT

MUST BE DISCARDED.

4) Never leave a coupler partially filled for an extended period of time. Make sure all couplers are filled completely and no

couplers are left ungrouted. Do not underfill the coupler. Place the grout into the coupler in one step – do not create a

cold joint in the coupler.

5) After grouting, keep the walls and panels undisturbed for at least 24 hours at 68°F (20°C). The final decision to

remove bracing is an engineering decision which must be determined solely by the structural engineer based on job

site conditions.

During cold weather grouting (temperature below 50°F; (10°C) the bracing time must be extended to at least 48

hours to allow the HY10L to gain the required strength.

6) Immediately following check grouting to make sure that no grout has leaked from the coupler.

Refer to the Trouble Shooting Guide located in this manual for additional guidelines.