Table 7. Communication Page Parameters and Values.
Menu Item

Display

Description

Range

Address

Communication
CommAddr

Sets address node for
control

1 to 247

Mode

Communication
Comm Mode

Turns on/off
communications

OFF, Modbus

Baud Rate

Communication
Baud Rate

Sets interface speed

2400, 4800, 9600,
19.2K, 38.4K

Parity

Communication
Parity

Sets parity for interface

None, Odd, Even

5.6.8.2. Setting up the Real Time Clock Page

The real time clock is a seven day, 24-hour clock with battery backup. The Real Time
Clock Page allows an operating mode to begin automatically at a specific time on a
specific day of the week. The real time clock feature also for use of the Power Failure
Recovery mode Time Limit feature (see Setting up the Control Page Section 5.6.7). Table
8
shows the menu items available.

5.6.8.3. Access Real Time Clock Page

1. Enter Setup Mode.
2. Press

Page

until

Clock

displays.

3. Press

Menu

.

4. Change each parameter by pressing

Menu

until the desired parameter is displayed,

and then press

▲ or ▼ to change the value.

Table 8. Real Time Clock Page Parameters and Values.
Menu
Item

Display

Description

Range

Day of the
week

Clock
Day

Setting for current day of the
week

Sun, Mon, Tue, Wed, Thu, Fri,
Sat

Time of
day

Clock
Hh:mm

Setting for current time of the
day

00:00 to 23:59

Reset
clock

Clock
UP to Reset

8

Press the

key to set the

clock to entered values

Ready, Done

5.6.9. Setting up the Relay Outputs Page

The Relay Outputs Page configures the four alarm/event outputs. Each output has a
dedicated indicator light and can be configured as a temperature alarm, profile event, or
end of cycle output. Temperature alarms can be of type process high, process low,
deviation high, deviation low, or deviation band. Table 9 shows the menu items available.

8

If the

▲ key is not pressed, clock values retain original values. The display changes to Done if the clock

is reset.