8 udp application: multi-point pair connection, Udp application: multi-point pair connection – Atop Technology SW550X User manual User Manual
Page 78
Atop Industrial Wireless Serial Device Server Series
SW550X
User Manual V 1.1
72
4.2.8 UDP Application: Multi-Point Pair Connection
It is also possible to setup pair connection in UDP mode to have more than one Pair
Connection Master or Slave to communicate to each other. For example, it is possible to setup
one Modbus Master and six Modbus Slaves in UDP, Fig. 4. 16. Note again that UDP does not
guarantee data delivery and only data would be transmitted over Ethernet; other serial pings
are not transmited. If RS-232 along with flow control, it is recommended to use Multi-Point Pair
Connection in TCP, see
Sec. 4.2.10
Note:
the destination IP and Port of the Slaves need to be equal to the Master’s IP and Port. Local Listening Port of
the
Slaves need to be equal to the Master’s Destination Port, see Table for an example.
Table 4. 1
IP Address
Link Mode
Local Listening Port
Destination IP
Destination Port
SW5501 Master COM1
10.0.50.100
UDP
5000
10.0.50.200~10.0.50.203
5000
SW5501 Master COM1
10.0.50.100
UDP
5001
10.0.50.200~10.0.50.201
5001
SW5502 Slave 1 COM1
10.0.50.200
UDP
5000
10.0.50.100
5000
SW5502 Slave 1 COM2
10.0.50.200
UDP
5001
10.0.50.100
5001
SW5502 Slave 2 COM1
10.0.50.201
UDP
5000
10.0.50.100
5000
SW5502 Slave 2 COM2
10.0.50.201
UDP
5001
10.0.50.100
5001
SW5501 Slave 3 COM1
10.0.50.202
UDP
5000
10.0.50.100
5000
SW5501 Slave 4 COM1
10.0.50.203
UDP
5000
10.0.50.100
5000