J.P. Instruments EDM 700/800/711 Pilots Guide User Manual
Page 46

Page 42
Engine Data Management
Section 14 - Alarm Limits
Factory Set Default Limits—Non-Primary
JPI conservatively sets the default alarm limits below Lycoming and
Continental recommendations.
Parameter
Default Low Limit
Default High Limit
Alarm Example
CHT
450°F*
230°C
465 CHT
OIL
90°F
32°C
230°F*
110°C
280 OIL
TIT
1650°F*
900°C
I720 TIT
CLD
-60°F/min.
-33°C/min.
-65 CLD
DIF
500°F
280°C
525 DIF
BAT, 24 V
24V
32V
22.4 BAT
BAT, 12 V
12V
16V
I7.6 BAT
MAP
32 inches
46.3 MAP
LO FUEL
45 min
00.20 H.M
LO TIME
10 gal, kg, ltr, lbs
7.2 REM
The alarm limits may differ from those shown here, depending on your type of aircraft.
If you change the display between Fahrenheit and Celsius, newer
instruments will automatically change the alarms to the factory limits.
When an alarm is displayed, tapping the STEP button will temporarily
delete that parameter from the sequence for the next ten minutes. When
an alarm is displayed, holding the STEP button until the word OFF
appears will delete that parameter from the sequence for the remainder
of the flight. On EDM-711 primary instruments the red alarm light
cannot be extinguished as long as the alarm condition is present.
Changing the Alarm Limits/Tank Capacity
You may prefer to set your own alarm limits or change your usable fuel
in the main tanks. Follow the procedure outlined below to change any of
the factory default settings.
To start the alarm limit procedure, after power up, wait until the EDM
completes its self test and is in the Automatic or Manual mode. If in
doubt, tap the STEP button a few times. Then follow the steps depicted
here: