Enter Pre-Operational
Through this service the NMT Master sets the state of the selected NMT Slaves to "PREOPERATIONAL".
This service is unconfirmed.
CS = 80h

Reset Node
Through this service the NMT Master initiates a "RESET APPLICATION" of the selected NMT Slaves from
any state. This service is unconfirmed.
CS = 81h

Reset Communication
Through this service the parameters of the communication profile area are set to their power-on values. After
this the state "INITIALISATION" is finished and the device executes the write boot-up object service and
enters the state PRE-OPERATIONAL.