6131h ai physical unit pv – WIKA D-21-9 User Manual
Page 31
D-20-9 / D-21-9
GB
WIKA Additional Instructions Pressure Transmitter with CANopen Interface D-20-9 / D-21-9
31
6131h AI Physical Unit PV
Object description
This object defines the physical unit of the process value.
Entry description
Sub-Index
00h
Name
number of entries
Access
ro
PDO Mapping
No
Data Type
UNSIGNED 8
Default Value
01h
Sub-Index
01h
Name
AI Physical Unit PV 1
Access
ro
PDO Mapping
No
Data Type
UNSIGNED 32
Default Value
00 4E 00 00h
Data
MSB
LSB
Prefix
(always 0)
SI Numerator
SI-Denumerator
(always 0)
reserved
(always 0)
The following units are supported:
22h: Pascal
4Eh: bar
A1h: at
A2h: mmH
2
O
A3h: mHG
A4h: atm
ABh: PSI
The settings take effect after a reset.
Changed parameters are not automatically stored, but they have to be stored via object 1010h Store
Parameters.
Furthermore the device can be reset to the factory settings via object 1011h Restore Default Parameters.