Input offset, Input autozero – WIKA D-21-9 User Manual
Page 37

D-20-9 / D-21-9
GB
WIKA Additional Instructions Pressure Transmitter with CANopen Interface D-20-9 / D-21-9
37
Input Offset
6124h AI_Input_Offset
For manual offset correction the detected offset is sent to the device, e.g. the device (pressure range 10 bar /
1,000,000 Pa) indicates 0.01 bar / 10,000 Pa at ambient pressure.
The user writes the determined offset to object 6124h subindex 1 (AI_Input_Offset_1),
i.e. in this example 10,000 Pa (=> 00 00 27 10 h)
ID
DLC
Byte0
Byte1
Byte2
Byte3
Byte4
Byte5
Byte6
Byte7
24h
61h
10h
27h
00h
00h
600h
+
Node-ID
8
CS =
22h
Index 6124h
01h
Subindex
desired value (as integer32)
The pressure transmitter confirms the successful service by:
ID
DLC
Byte0
Byte1
Byte2
Byte3
Byte4
Byte5
Byte6
Byte7
24h
61h
580h
+
Node-ID
8
CS =
60h
Index 6124h
01h
Subindex
00h
00h
00h
00h
Changed parameters are not automatically stored, but they have to be stored via object 1010h Store
Parameters.
Furthermore the device can be reset to the factory settings via object 1011h Restore Default Parameters.
Input Autozero
6125h AI_Input_Autozero
The zero (pressure = 0) is changed to the actual pressure.
ID
DLC
Byte0
Byte1
Byte2
Byte3
Byte4
Byte5
Byte6
Byte7
25h
61h
7Ah
65h
72h
6F
600h
+
Node-ID
8
CS =
22h
Index 6125h
01h
Subindex
“zero” (ASCII)
The pressure transmitter confirms the successful service by:
ID
DLC
Byte0
Byte1
Byte2
Byte3
Byte4
Byte5
Byte6
Byte7
25h
61h
580h
+
Node-ID
8
CS =
60h
Index 6125h
01h
Subindex
00h
00h
00h
00h
Changed parameters are not automatically stored, but they have to be stored via object 1010h Store
Parameters.
Furthermore the device can be reset to the factory settings via object 1011h Restore Default Parameters.