D-20-9 / D-21-9

GB

WIKA Additional Instructions Pressure Transmitter with CANopen Interface D-20-9 / D-21-9

14

1014h COB-ID Emergency Object

Object description

This Index defines the COB-ID of the Emergency Object (EMCY).

Entry description

Access

ro

PDO Mapping

No

Data Type

UNSIGNED 32

Default Value

80h + Node-ID

Data

MSB

LSB

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0

always 0

11-bit identifier (80h)

0 : 11-bit identifier

0 : reserved (always 0)

0 : EMCY exists / is valid

1017h Producer Heartbeat Time

Object description

The producer heartbeat time defines the cycle time of the heartbeat in milliseconds. The producer heartbeat
time is 0 if it is not used.

Entry description

Access

rw*

PDO Mapping

No

Data Type

UNSIGNED 16

Default Value

0

* Write access to this object is only allowed, if object 100Ch Guard Time and 100Dh Life Time Factor are 0.

Changed parameters are not automatically stored, but they have to be stored via object 1010h Store
Parameters.
Furthermore the device can be reset to the factory settings via object 1011h Restore Default Parameters.

Data

MSB

LSB

00h

00h

Producer Heartbeat

Time in ms