Network management objects, Module control services – WIKA D-21-9 User Manual
Page 40

D-20-9 / D-21-9
GB
WIKA Additional Instructions Pressure Transmitter with CANopen Interface D-20-9 / D-21-9
40
9. Network Management Objects
Module Control Services
Through Module Control Services, the NMT master controls the state of the NMT slaves. The state attribute is
one of the values {STOPPED, PRE-OPERATIONAL, OPERATIONAL and INITIALISING}. The Module Control
Services can be performed with a certain node or with all nodes simultaneously. The NMT master controls its
own NMT state machine via local services, which are implementation dependent.
Module Control Protocol
NMT Master request
ID
DLC
Byte0
Byte1
00h
2
CS
Node-ID
(0 = all
slaves)
CS: NMT command specifier
NMT services are unconfirmed.
Start Remote Node
Through this service the NMT Master sets the state of the selected NMT Slaves to "OPERATIONAL".
CS = 01h
Stop Remote Node
Through this service the NMT Master sets the state of the selected NMT Slaves to "STOPPED". This service
is unconfirmed.
CS = 02h