beautypg.com

Horizontal installation, Heat controller, inc. hbh series iom manual – Comfort-Aire HBH Series 6-10 Tons User Manual

Page 7

background image

Heat Controller, Inc.

HBH SERIES

IOM Manual

6

Horizontal Installation

Figure 1: Hanger Bracket

Figure 2: Horizontal Unit Pitch

3/8" [10mm] Threaded

Rod (by others)

Vibration Isolator

(factory supplied)

Washer

(by others)

Double Hex Nuts

(by others)

Varilla Roscada de 3/8"

(fabricada por terceros)

Arandela

(fabricada por terceros)

Tuercas Hexagonales
Dobles (por terceros)

Instale los Tornillos como
se Indica en el Diagrama

La longitud de este tornillo

debe ser de solamente 1/2” para evitar daños

Aislador de Vibraciones
(para codificación por color y
notas de instalación, consulte
las instrucciones de
instalación del soport
e colgador)

1/4" [6.4mm] pitch
for drainage

Drain

Connection

Horizontal Unit Location - Units are not designed for

outdoor installation. Locate the unit in an INDOOR area

that allows enough space for service personnel to perform

typical maintenance or repairs without removing unit from

the ceiling. Horizontal units are typically installed above

a false ceiling or in a ceiling plenum. Never install units in

areas subject to freezing or where humidity levels could

cause cabinet condensation (such as unconditioned

spaces subject to 100% outside air). Consideration should

be given to access for easy removal of the filter and

access panels. Provide sufficient room to make water,

electrical, and duct connection(s). Allow 3 feet (91 cm)

clearance for servicing unit through all access panels.

If the unit is located in a confined space, such as a closet,

provisions must be made for return air to freely enter the

space by means of a louvered door, etc. Any access panel

screws that would be difficult to remove after the unit is

installed should be removed prior to setting the unit. Refer

to Figure 3 for an illustration of a typical installation. Refer

to unit submittal data or engineering design guide for

dimensional data.

Conform to the following guidelines when selecting

unit location:

1. Provide a hinged access door in concealed-spline

or plaster ceilings. Provide removable ceiling

tiles in T-bar or lay-in ceilings. Refer to horizontal

unit dimensions for specific series and model in

unit submittal data. Size the access opening to

accommodate the service technician during the

removal or replacement of the compressor and the

removal or installation of the unit itself.

2. Provide access to hanger brackets, water valves

and fittings. Provide screwdriver clearance to

access panels, discharge collars and all electrical

connections.

3. DO NOT obstruct the space beneath the unit with

piping, electrical cables and other items that prohibit

future removal of components or the unit itself.

4. Use a manual portable jack/lift to lift and support the

weight of the unit during installation and servicing.

The installation of water source heat pump units and all

associated components, parts and accessories which

make up the installation shall be in accordance with

the regulations of ALL authorities having jurisdiction

and MUST conform to all applicable codes. It is the

responsibility of the installing contractor to determine and

comply with ALL applicable codes and regulations.

Mounting Horizontal Units - Horizontal units have hanger

kits pre-installed from the factory as shown in Figure 1.

Figure 3 shows a typical horizontal unit installation.

Horizontal heat pumps are typically suspended above a

ceiling or within a soffit using field supplied, threaded rods

sized to support the weight of the unit.

Use four (4) field supplied threaded rods and factory

provided vibration isolators to suspend the unit. Hang the

unit clear of the floor slab above and support the unit by

the mounting bracket assemblies only. DO NOT attach the

unit flush with the floor slab above.

Pitch the unit toward the drain as shown in Figure 2 to

improve the condensate drainage.