beautypg.com

Ground-water heat pump applications – Comfort-Aire HBH Series 6-10 Tons User Manual

Page 16

background image

IOM Manual

HBH SERIES

Heat Controller, Inc.

15

Open Loop - Ground Water Systems - Typical open loop

piping is shown in Figure 10. Shut off valves should be

included for ease of servicing. Boiler drains or other valves

should be “tee’d” into the lines to allow acid flushing of the

heat exchanger. Shut off valves should be positioned to

allow flow through the coax via the boiler drains without

allowing flow into the piping system. P/T plugs should

be used so that pressure drop and temperature can be

measured. Piping materials should be limited to copper or

PVC SCH80. Note: Due to the pressure and temperature

extremes, PVC SCH40 is not recommended.

Water quantity should be plentiful and of good quality.

Consult table 3 for water quality guidelines. The unit can

be ordered with either a copper or cupro-nickel water

heat exchanger. Consult Table 3 for recommendations.

Copper is recommended for closed loop systems and open

loop ground water systems that are not high in mineral

content or corrosiveness. In conditions anticipating heavy

scale formation or in brackish water, a cupro-nickel heat

exchanger is recommended. In ground water situations

where scaling could be heavy or where biological growth

such as iron bacteria will be present, an open loop system

is not recommended. Heat exchanger coils may over time

lose heat exchange capabilities due to build up of mineral

deposits. Heat exchangers must only be serviced by a

qualified technician, as acid and special pumping equipment

is required. Desuperheater coils can likewise become scaled

and possibly plugged. In areas with extremely hard water,

the owner should be informed that the heat exchanger

may require occasional acid flushing. In some cases, the

desuperheater option should not be recommended due to

hard water conditions and additional maintenance required.

Water Quality Standards - Table 3 should be consulted

for water quality requirements. Scaling potential should be

assessed using the pH/Calcium hardness method. If the pH

<7.5 and the calcium hardness is less than 100 ppm, scaling

potential is low. If this method yields numbers out of range

of those listed, the Ryznar Stability and Langelier Saturation

indecies should be calculated. Use the appropriate scaling

surface temperature for the application, 150°F [66°C] for

direct use (well water/open loop) and DHW (desuperheater);

90°F [32°F] for indirect use. A monitoring plan should

be implemented in these probable scaling situations.

Other water quality issues such as iron fouling, corrosion

prevention and erosion and clogging should be referenced in

Table 3.

Expansion Tank and Pump - Use a closed, bladder-type

expansion tank to minimize mineral formation due to air

exposure. The expansion tank should be sized to provide

at least one minute continuous run time of the pump using

its drawdown capacity rating to prevent pump short cycling.

Discharge water from the unit is not contaminated in any

manner and can be disposed of in various ways, depending

on local building codes (e.g. recharge well, storm sewer,

drain field, adjacent stream or pond, etc.). Most local codes

forbid the use of sanitary sewer for disposal. Consult your

local building and zoning department to assure compliance

in your area.

Water Control Valve - Note the placement of the water

control valve in Figure 10. Always maintain water pressure

in the heat exchanger by placing the water control valve(s)

on the discharge line to prevent mineral precipitation

during the off-cycle. Pilot operated slow closing valves are

recommended to reduce water hammer. If water hammer

persists, a mini-expansion tank can be mounted on the

piping to help absorb the excess hammer shock. Insure that

the total ‘VA’ draw of the valve can be supplied by the unit

transformer. For instance, a slow closing valve can draw up

to 35VA. This can overload smaller 40 or 50 VA transformers

depending on the other controls in the circuit. A typical pilot

operated solenoid valve draws approximately 15VA (see

Figure 14). Note the special wiring diagrams for slow closing

valves (Figures 15 & 16).

Flow Regulation - Flow regulation can be accomplished

by two methods. One method of flow regulation involves

simply adjusting the ball valve or water control valve on

the discharge line. Measure the pressure drop through the

unit heat exchanger, and determine flow rate from Tables

8a through 8e. Since the pressure is constantly varying,

two pressure gauges may be needed. Adjust the valve

until the desired flow of 1.5 to 2 gpm per ton [2.0 to 2.6

l/m per kW] is achieved. A second method of flow control

requires a flow control device mounted on the outlet of the

water control valve. The device is typically a brass fitting

with an orifice of rubber or plastic material that is designed

to allow a specified flow rate. On occasion, flow control

devices may produce velocity noise that can be reduced by

applying some back pressure from the ball valve located

on the discharge line. Slightly closing the valve will spread

the pressure drop over both devices, lessening the velocity

noise.

NOTE: When EWT is below 50°F [10°C], 2 gpm

per ton (2.6 l/m per kW) is required.

Ground-Water Heat Pump Applications