Hbh120 blower performance, Iom manual hbh series heat controller, inc – Comfort-Aire HBH Series 6-10 Tons User Manual
Page 34

IOM Manual
HBH SERIES
Heat Controller, Inc.
33
SCFM
ESP
0.00
0.10
0.20
0.30
0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40
1.50
3000
BHP
0.75
0.81
0.86
0.91
0.97
1.03
1.09
1.15
1.21
1.27
1.34
1.41
1.47
1.54
1.61
1.67
Sheave/Mtr
B
B
B
B
B
B
A
A
A
A
A
A
A
A
A
A
RPM
680
720
755
790
825
860
895
925
955
985
1015
1045
1070
1100
1130
1155
Turns Open
5
4
3.5
3
2.5
1.5
5.5
5
4.5
4
3.5
3
2.5
2
1.5
1
3100
BHP
0.82
0.88
0.94
0.99
1.04
1.10
1.17
1.26
1.33
1.40
1.46
1.53
1.59
1.66
1.72
1.80
Sheave/Mtr
B
B
B
B
B
A
A
A
A
A
A
A
A
A
A
C
RPM
700
735
775
805
840
875
905
940
970
1000
1025
1055
1080
1110
1135
1165
Turns Open
4.5
4
3
2.5
2
6
5.5
4.5
4.5
3.5
3
3
2.5
2
1.5
4
3200
BHP
0.90
0.96
1.03
1.10
1.17
1.23
1.29
1.35
1.41
1.47
1.55
1.61
1.68
1.74
1.81
1.89
Sheave/Mtr
B
B
B
B
B
A
A
A
A
A
A
A
A
A
A
C
RPM
720
755
790
825
860
890
920
950
980
1010
1040
1065
1095
1120
1145
1175
Turns Open
4
3.5
3
2
1.5
5.5
5
4.5
4
3.5
3
2.5
2
1.5
1
3.5
3300
BHP
0.98
1.04
1.11
1.18
1.25
1.31
1.37
1.43
1.49
1.55
1.62
1.68
1.75
1.81
1.88
1.95
Sheave/Mtr
B
B
B
B
A
A
A
A
A
A
A
A
A
A
A
C
RPM
740
770
805
840
875
905
935
965
995
1020
1050
1075
1105
1130
1155
1180
Turns Open
4
3
2.5
2
6
5.5
5
4
4
3
2.5
2.5
2
1.5
1
3.5
3400
BHP
1.06
1.13
1.19
1.26
1.33
1.38
1.44
1.50
1.56
1.65
1.72
1.80
1.87
1.94
2.00
2.06
Sheave/Mtr
B
B
B
B
A
A
A
A
A
A
A
A
A
A
C
C
RPM
755
790
820
855
890
915
945
975
1005
1035
1060
1090
1115
1140
1165
1190
Turns Open
3.5
3
2.5
1.5
6
5
4.5
4
3.5
3
2.5
2
1.5
1
4
3
3500
BHP
1.14
1.21
1.27
1.34
1.40
1.46
1.52
1.58
1.65
1.71
1.77
1.84
1.90
1.98
2.06
2.14
Sheave/Mtr
B
B
B
A
A
A
A
A
A
A
A
A
A
A
C
C
RPM
770
805
835
870
900
930
960
990
1020
1045
1070
1100
1125
1150
1175
1200
Turns Open
3
2.5
2
6
5.5
5
4.5
3.5
3.5
3
2.5
2
1.5
1
3.5
3
3600
BHP
1.23
1.29
1.36
1.42
1.50
1.57
1.64
1.71
1.77
1.84
1.90
1.96
2.05
2.13
2.21
2.27
Sheave/Mtr
B
B
B
A
A
A
A
A
A
A
A
A
A
C
C
C
RPM
790
820
855
885
915
945
975
1005
1030
1060
1085
1110
1140
1165
1190
1210
Turns Open
3
2.5
1.5
6
5.5
4.5
4
3.5
3
2.5
2
1.5
1.5
4
3.5
3
3700
BHP
1.32
1.38
1.44
1.51
1.58
1.65
1.73
1.81
1.88
1.96
2.03
2.10
2.18
2.26
2.34
2.42
Sheave/Mtr
B
B
A
A
A
A
A
A
A
A
A
A
A
C
C
C
RPM
810
840
870
900
930
960
990
1020
1045
1075
1100
1125
1150
1175
1200
1225
Turns Open
2.5
2
6
5.5
5
4.5
4
3
3
2.5
2
1.5
1
3.5
3
2.5
3800
BHP
1.41
1.47
1.54
1.61
1.68
1.75
1.82
1.91
1.99
2.07
2.17
2.25
2.31
2.39
2.47
2.55
Sheave/Mtr
B
B
A
A
A
A
A
A
A
A
A
A
A
C
C
C
RPM
830
860
890
920
950
980
1005
1035
1060
1085
1115
1140
1160
1185
1210
1235
Turns Open
2
1.5
5.5
5
4.5
4
3.5
3
2.5
2
1.5
1
1
3.5
3
2.5
3900
BHP
1.54
1.60
1.67
1.74
1.82
1.89
1.96
2.04
2.14
2.22
2.30
2.38
2.46
2.52
2.60
2.68
Sheave/Mtr
B
A
A
A
A
A
A
A
A
A
A
A
C
C
C
C
RPM
850
875
905
935
965
995
1020
1045
1075
1100
1125
1150
1175
1195
1220
1245
Turns Open
2
6
5.5
5
4.5
3.5
3
2.5
2.5
2
1.5
1
3.5
3
2.5
2
4000
BHP
1.63
1.71
1.78
1.86
1.94
2.03
2.11
2.19
2.27
2.37
2.45
2.51
2.59
2.67
2.75
2.85
Sheave/Mtr
A
A
A
A
A
A
A
A
A
A
A
A
C
C
C
C
RPM
865
895
920
950
980
1010
1035
1060
1085
1115
1140
1160
1185
1210
1235
1260
Turns Open
6
5.5
5
4.5
4
3.5
3
2.5
2
1.5
1
1
3.5
3
2.5
2
4100
BHP
1.73
1.81
1.90
1.97
2.05
2.12
2.20
2.27
2.34
2.42
2.52
2.62
2.70
2.80
2.90
Sheave/Mtr
A
A
A
A
A
A
A
A
A
A
A
C
C
C
C
RPM
885
915
945
970
1000
1025
1055
1080
1105
1130
1155
1180
1200
1225
1250
Turns Open
6
5.5
4.5
4
4
3
2.5
2
2
1.5
1
3.5
3
2.5
2
4200
BHP
1.87
1.94
2.02
2.08
2.16
2.24
2.32
2.40
2.48
2.58
2.68
2.76
2.86
2.96
Sheave/Mtr
A
A
A
A
A
A
A
A
A
A
C
C
C
C
RPM
905
935
965
990
1020
1045
1070
1095
1120
1145
1170
1190
1215
1240
Turns Open
5.5
5
4.5
4
3.5
3
2.5
2
1.5
1
3.5
3.5
3
2.5
HBH120 Blower Performance
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require field selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airflow in rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.