The door peripherals identified in “Step 1 - Identify System Components” on page 2 should be directly connected to the I/O

ports of the EH400-K. The I/O ports may be configured to provide the following output current capacity.

Device

Ports

Conditions

I out

EDGE EVO Hi-O Standard Network

Controller (EH400-K)

Strike / Aux

NC or NO

DC Output

+12VDC unregulated

(@ +12VDC EDM-M input)

600 mA*

+24VDC unregulated

(@ +24VDC EDM-M input)

600 mA*

+12VDC regulated

(@ +24VDC EDM-M input)

3 mA*

Dry Jumpers

+12VDC to +24VDC External

2.00 Amp**

Reader Power

+9.8VDC to +12.25 VDC

320-600mA*

* = Combined output ratings, not to exceed 1.2 Amp
** = Each relay
Ensure door peripherals connected to the Strike/AUX relays (regulated/unregulated) do not exceed 1.2 Amps combined.

Alternatively, the door peripherals may be connected to the Strike/AUX relays configured for Dry contact up to 2 Amps.
Ensure Wiegand / Clock-and-Data readers attached to the reader port do not exceed:

320mA @ +9.8VDC

or

600mA @ +12.25VDC