Standard Networked Controller

EH400-K

Step 3 - Analyze Power Requirements

A - Door Peripheral Operational Currents

For the door peripherals identified in “Step 1 - Identify System Components” on page 2, consult the vendor data sheets

to determine the operational current draw. Typical operational current draw is provided below.
Note: See individual peripheral data sheets for actual operational current draw.

Device

Conditions

Typical Operational Current

Door Position Switch

V

in

= 12VDC

15mA

(For example, Securitron MSS) V

in

= 24VDC

15mA

Mag Lock

V

in

= 12VDC

300mA

(For example, Securitron M32)

V

in

= 24VDC

150mA

REX Switch

V

in

= 12VDC

28mA

(For example, Securitron EEB)

V

in

= 24VDC

38mA

iCLASS Wiegand Reader

V

in

= 12VDC

150mA

B - Match I/O Requirements to the Hi-O Interface Device

For the door peripherals identified in “Step 1 - Identify System Components” on page 2, the system requires direct

connection to I/O interface and Wiegand/Clock-and-Data ports of the EH400-K. A separate Hi-O Interface Device is not

required.

C - Compute and Compare Overall Current Draw

Calculate the total current draw for all door peripherals and the attached Wiegand readers with the following equation,

adding terms as required.

I

total

= I

dps

+ I

mag

+ I

rex

+ … + I

iCLASS reader

The following calculations provide load current computations.

I

total

@ 12VDC = 15mA + 300mA + 28mA + 150mA = 493mA

I

total

@ 24VDC = 15mA + 150mA + 38mA + 150mA = 353mA

Compare the required current draw (I

total

) to the output current capacity of the EH400-K (see Specification table, pg 1) to

select the Eh400-K power scheme. The CAN DC Pwr Output represents the entire power output capacity of the EH400-K.

Device

Port

Conditions

Vout

I out

Standard Networked Controller
(EH400-K)

CAN DC PWR

Output (MAX)

AUX 12-24VDC Input

+10.8 to +24VDC

1.2A

PoE input

+24VDC (NOM)

400mA

In this example, the EH400-K provides sufficient power when operated with a PoE injector, or +12/24VDC auxiliary power

supplies.
Directly connect the door peripherals identified in “Step 1 - Identify System Components” on page 2 to the EH400-K I/O

ports per the “Specifications” on page 1 for the selected input power scheme.
Ensure all door peripherals connected to the Strike/AUX relays and the Reader DC Pwr Output or both do not exceed

1.2Amps (AUX Input) or 0.4Amps (PoE Input), combined. Alternatively, the door peripherals may be connected to the Strike/

AUX relays configured for Dry contact up to 2Amps per relay.