Input/output wiring – single mains (default), Wiring procedure – single mains – American Power Conversion 10-30 KVA User Manual

Page 34

background image

28

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

990-1598B

Input/Output Wiring – Single Mains (default)

The UPS is designed for both single (default) and dual mains installations. Follow the below steps to
install the UPS in a single-mains installation.

Wiring procedure – single mains

 Loosen the (6) M4 screws from the cover of the cable termination area on the rear, and remove.

 Loosen the (2) M4 screws (1 each side) from the top part of the Conduit Box. Loosen the M4

screws attaching it to the bottom part (2 screws in a 13.8 5in/352 mm Enclosure, 3 screws in a
20.59 in/523 mm Enclosure), and remove.

Note

The illustrations show a 20.59 in/523 mm Enclosure, but installation procedures are
identical for 13.85 in/352 mm Enclosures).

N

N

Conduit box
(bottom part)

Conduit box
(top part)

Out

put

Input

EPO
Conduit

MBP
Conduit