Site Preparation – Operating Environment

14

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

990-1598B

Minimum breaker settings for 15 kVA UPS

Note 1: For the output value, the short-circuit-level is indicated

Minimum breaker settings for 20 kVA UPS

Note 1: For the output value, the short-circuit-level is indicated.

Minimum setting of breakers for 30 kVA UPS

Note 1: For the output value, the short-circuit level is indicated.

Overload Event

Mains input

Bypass input

Output

Duration

Notes

Internal fault

2.5 kA

2.1 kA

14 kA

<10 ms

1

800% overload bypass
operation

333 A

333 A

500 ms

150% overload normal/
battery operation

63 A

30 s

125% overload normal/
battery operation

52 A

60 s

Continuously

51 A

46 A

46 A

Overload Event

Mains input

Bypass input

Output

Duration

Notes

Internal fault

4 kA

3.4 kA

14 kA

<10 ms

1

800% overload bypass
operation

444 A

444 A

500 ms

150% overload normal/
battery operation

84 A

30 s

125% overload normal/
battery operation

70 A

60 s

Continuously

68 A

62 A

62 A

Overload Event

Mains input

Bypass input

Output

Duration

Notes

Internal fault

5 kA

4.2 kA

14 kA

<10 ms

1

800% overload bypass
operation

667 A

667 A

500 ms

150% overload normal/battery
operation

125 A

30 s

125% overload normal/battery
operation

105 A

60 s

Continuously

102 A

92 A

92 A