Electrical Installation – System-Electrical Information

990-1598B

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

23

UPS ratings 220 V

10 kVA
8 kW

15 kVA
12 kW

20kVA
16 kW

30 kVA
24 kW

Input voltage / Bypass voltage (V)

3-phase
220Y/
127 V

3-phase
220Y/
127 V

3-phase
220Y/
127 V

3-phase
220Y/
127 V

Input current (nominal, per phase) (A)

22.9

34.6

46.5

68.9

Maximum input current per phase (continuous, at
minimum mains voltage)

25.2

38.0

50.1

75.8

Input current protection for mains source or single
mains supply (external to UPS, not supplied) (A)

3x35

3x60 3x80 3x125

Input current protection for bypass source in dual mains
configuration (external to UPS, not supplied) (A)

35 60 80 125

Input frequency (Hz) range

40-70

40-70

40-70

40-70

Output voltage (on line). (V)
Minimum and maximum values (+/- 1%)

127/220

127/220

127/220

127/220

Output current (nominal, per phase) (A)

26.2

39.4

52.5

78.7

Maximum output current
(in bypass only at 110% overload per phase)

28.9

43.3

57.7

86.6

Neutral output current (with 100% switch mode load)
(A)

45.5

68.2

90.9

136.4

Output current protection (external to UPS, not
supplied) (A)

40 60 80 120

Output frequency range (Hz)

50/60

50/60

50/60

50/60

DC overcurrent protection and disconnect switch for
external safety:
DC voltage rating of the battery supply
Maximum available short-circuit current

26.4

+/- 192
10 kA

39.6

+/- 192
10 kA

52.7

+/- 192
10 kA

78.9

+/- 192
10 kA