Site Preparation – Operating Environment

990-1598B

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

15

Recommended phase-conductor sizes [AWG] for a 86°F (30°C) temperature

environment

)

EPO switch wiring

The UPS must be connected to either a dry contact or a 24V

DC

Emergency Power Off (EPO) switch.

UPS/AWG sizes

Mains input

[AWG]

AC output

[AWG]

DC input

[AWG], 75°C Wire

10 kVA

8

8

1

15 kVA

6

6

1

20 kVA

4

4

1

30 kVA

1

1

1

Note

Use Molex lug type or equivalent, and crimp to manufacturer’s specifications.

Cable Size

[AWG]

Cable Lug Type

Crimping Tool

Die

Terminal Bolt

Diameter

12

YA12CL2TC38

MD7-34R

W12CVT

0.2 in/6 mm

8

YA8CL2TC38

MD7-34R

W8CVT

0.2 in/6 mm

6

YA6CL2TC38

MD7-34R

W5CVT

0.2 in/6 mm

4

YA4CL2TC38

MD7-34R

W4CVT

0.2 in/6 mm

1

YA1CL2TC38

MD7-34R

W1CVT

0.2 in/6 mm

WARNING!
At 100% non-liniear load (EN50091-3 standard), the neutral shall be rated for 200%
phase current.

See “Pin connections J108 (for EPO wiring options)” on page 37