Electrical installation, System-electrical information – American Power Conversion 10-30 KVA User Manual

Page 28

background image

22

Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

990-1598B

Electrical Installation

System-Electrical Information

WARNING!
All electrical power and power control wiring must be installed by a qualified electrician,
and must comply with local and national regulations for maximum power rating.

UPS ratings 208 V

10 kVA
8 kW

15 kVA
12 kW

20kVA
16 kW

30 kVA
24 kW

Input voltage / Bypass voltage (V)

3-phase
208Y/
120 V

3-phase
208Y/
120 V

3phase
208Y/
120 V

3-phase
208Y/
120 V

Input current (nominal, per phase) (A)

24.3

36.5

48.2

72.9

Maximum input current per phase (continuous, at
minimum mains voltage)

26.7

40.2

53.0

80.1

Input current protection for mains source or single
mains supply (external to UPS, not supplied) (A)

3x35 3x60 3x80 3x125

Input current protection for bypass source in dual mains
configuration (external to UPS, not supplied) (A)

35 60 80 125

Input frequency (Hz) range

40-70

40-70

40-70

40-70

Output voltage (on line). (V)
Minimum and maximum values (+/- 1%)

120/208 120/208

120/208

120/208

Output current (nominal, per phase) (A)

27.8

41.6

55.5

83.3

Maximum output current
(in bypass only at 110% overload per phase)

30.5

45.8

61.1

91.6

Neutral output current (with 100% switch mode load)
(A)

48.1

72.1

96.2

144.2

Output current protection (external to UPS, not
supplied) (A)

40 60 80 120

Output frequency range (Hz)

50/60

50/60

50/60

50/60

DC overcurrent protection and disconnect switch for
external safety:
DC voltage rating of the battery supply
Maximum available short-circuit current

27.8

+/- 192
10 kA

41.8

+/- 192
10 kA

55.7

+/- 192
10 kA

83.5

+/- 192
10 kA