Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual

990-1598B

Operating Environment

Operating conditions

Heat dissipation

Audible noise

Note

Install the UPS in an indoor, temperature-controlled area, free of conductive
contaminants.

Temperature

Range:

32° to 104°F /

0° to 40°C

Keep Ventilated

Front-to-Rear

Airflow (see

space

considerations)

Relative

Humidity: <95%

Non-condensing

No Conductive

Dust or

Corrosive

Fumes

Altitude derating table:

3,000 ft/914 m: 100% load
4,500 ft/1371 m: 95% load
6,000 ft/1828 m: 91% load
8,000 ft/2438 m: 86% load

10,000 ft/3048 m: 82% load

UPS size

BTU/hr at fully

charged batteries

UPS size

BTU/hr at fully

charged batteries

10 kVA

1,774

20 kVA

3,624

15 kVA

2,866

30 kVA

5,486

UPS Sizes

Audible noise at 100% load

(1.09 yard/1 m from the UPS)

Audible noise at <70% load

(1.09 yard/1 m from the UPS)

10-15 kVA

54 dBA

45.4 dBA

20-30 kVA

58 dBA

48.5 dBA