Appendix: Multiple SmartSlot Installation

If your UPS configuration uses more than one SmartSlot device, you
must install them in the correct order for them to work together properly.

A SmartSlot device with higher priority is to be placed in the SmartSlot
labeled with the higher number. Refer to the table that follows.

2

3

1

Status

Power

Monitoring Port

To UPS

24 VDC

+

Management Port

Status

AP9608 Call-UPS Remote Mgt Device

Smart Slot

Smart Slot

Smart Slot

Smart Slot

Reset

Status

Link - RX/TX

AP9605 PowerNet™ SNMP Adapter™

Smart Slot

Smart Slot

Probes

1 2

Sensor Zones

AP9612 Measure-UPS™

1 2 3 4

GND

DEVICE

PART #

PRIORITY

POSITION

PowerNet SNMP

Adapter

AP9605

Highest

Highest-numbered slot.

Call-UPS II

Remote UPS

Management Device

AP9608

Second

Highest

Second-highest-numbered
slot (highest if no PowerNet
SNMP Adapter is present).

Relay I/O Module

AP9610

Medium

Any slot numbered lower
than PowerNet SNMP
Adapter & Call-UPS II and
higher than Measure-UPS.

Interface Expander

AP9607

Medium

Any slot numbered lower
than PowerNet SNMP
Adapter & Call-UPS II and
higher than Measure-UPS.

Measure-UPS

AP9612TH

Lowest

Lowest numbered slot.

Triple Chassis

To install SmartSlot devices in the

APC

Triple Chassis (

AP9604

), note

that the slots are numbered on the rear panel. The following figure shows
the rear panel of the Triple Chassis with the PowerNet

SNMP

Adapter

installed in slot #3, Call-

UPS II

in slot #2 and Measure-

UPS

II in slot #1.