Appendix: multiple smartslot installation, Device part # priority position, Triple chassis – APC AP9608 User Manual
Page 46: Adapter installed in slot #3, call, Ii in slot #1, Ap9604, Snmp, Ups ii

42
Appendix: Multiple SmartSlot Installation
If your UPS configuration uses more than one SmartSlot device, you
must install them in the correct order for them to work together properly.
A SmartSlot device with higher priority is to be placed in the SmartSlot
labeled with the higher number. Refer to the table that follows.
2
3
1
Status
Power
Monitoring Port
To UPS
24 VDC
–
+
–
Management Port
Status
AP9608 Call-UPS Remote Mgt Device
Smart Slot
Smart Slot
Smart Slot
Smart Slot
Reset
Status
Link - RX/TX
AP9605 PowerNet™ SNMP Adapter™
Smart Slot
Smart Slot
Probes
1 2
Sensor Zones
AP9612 Measure-UPS™
1 2 3 4
GND
DEVICE
PART #
PRIORITY
POSITION
PowerNet SNMP
Adapter
AP9605
Highest
Highest-numbered slot.
Call-UPS II
Remote UPS
Management Device
AP9608
Second
Highest
Second-highest-numbered
slot (highest if no PowerNet
SNMP Adapter is present).
Relay I/O Module
AP9610
Medium
Any slot numbered lower
than PowerNet SNMP
Adapter & Call-UPS II and
higher than Measure-UPS.
Interface Expander
AP9607
Medium
Any slot numbered lower
than PowerNet SNMP
Adapter & Call-UPS II and
higher than Measure-UPS.
Measure-UPS
AP9612TH
Lowest
Lowest numbered slot.
Triple Chassis
To install SmartSlot devices in the
APC
Triple Chassis (
AP9604
), note
that the slots are numbered on the rear panel. The following figure shows
the rear panel of the Triple Chassis with the PowerNet
SNMP
Adapter
installed in slot #3, Call-
UPS II
in slot #2 and Measure-
UPS
II in slot #1.