Paging setup setting default description – APC AP9608 User Manual
Page 37

33
----------------------- PAGING SETUP ------------------------
1-
Paging:
ON
2- Dial String 1:
DT9,5551212@
3- Dial String 2:
DT9,5551212@
4-
Repeat 1:
1
8-
Site ID:
12345678
5-
Repeat 2:
1
9- Space Char:
*
6- Page Interval:
1 min
10- Dial Speed:
Slow
7- Message Delay:
15 sec
11- End String:
--- EVENT ------ NUM:
1 2 CODE -- EVENT--NUM:
1 2 CODE
12-
UPS ON-BATTERY
Y N 0
20- ZONE 1
Y N
8
13-
ON & LOW BATTER
Y N 1
21- ZONE 2
Y N
9
14-
UPS SHUT DOWN
Y N 2
22- ZONE 3
Y N 10
15-
UPS ON-LINE
Y N 3
23- ZONE 4
Y N 11
16-
REPLACE BATTERY
Y N 4
24- ZONES CLEARY N 12
17-
UPS FAULT
Y N 5
25- PROBE 1
Y N 13
18-
LOST COM W/ UPS
Y N 6
26- PROBE 2
Y N 14
19-
BYPASS
Y N 7
27- PROBES CLEARY N 15
-------------------------------------------------------------
?-
Help
Return to Previous menu
>
PAGING SETUP
Setting
Default
Description
Paging
OFF
To enable paging, enter 1 when prompted. Enter 0 to
disable.
Dial
String 1
DT9,
5551212@
Dial string for the pager (the first pager if two are
used). Use standard modem commands such as:
DP — dial in pulse mode; DT — dial in tone mode
W — wait for second dial tone; , (Comma) — pause
(typically for 2 seconds); @ — wait for a quiet
answer (5 seconds of silence)
Dail
String 2
DT9,
5551212@
Dial string for a second pager number.
Repeat 1
1
Number of times, from 0–4, that the page for the first
pager number is repeated. Call-UPS II cycles through
Repeat 1, Repeat 2, and Page Interval for each report-
able event. Events are buffered and p rioritized during
paging to keep the operator updated with the best
information. Note: paging is also controlled on an
event basis (see later chart). Set Repeat to 0 to dis-
able a pager without having to disable all the events.
Repeat 2
1
Same as Repeat 1, for pager associated with Dial
String 2.