APC AP9608 User Manual
Page 25
21
If the
UPS
is powered off when
UPS
Control is selected from the Main
menu, Call-
UPS II
responds with an abbreviated control menu:
Type 1 to turn the
UPS
on, then press
ESC
to return to the Main menu or
press
ENTER
to re-display the full
UPS
Control menu.
UPS CONTROL (Continued)
Command
Description
Graceful Turn
OFF
Causes the UPS to shut down. Call-UPS II immediately
signals that the UPS is on battery and that the battery is
nearly exhausted. Graceful Turn OFF uses the value set for
Low Battery Duration. See UPS Characteristics table in
Sec. 4.4.
Start(Stop)
Runtime
Calibration
Starts and stops runtime calibration on the UPS.
Calibration starts only if the UPS has a 100% battery
charge. If the UPS accepts the command to start runtime
calibration, Call-UPS II reports “Runtime Calib: OK.” If
the UPS does not accept the command, Call-UPS II
reports “Runtime Calib: NO.” Runtime is displayed on the
UPS Status [and Diagnostics] Screen. Note: Smart-UPS
products with serial numbers that begin with the letter W
do not support runtime calibration.
Put UPS in
(Return from)
Bypass
For Matrix-UPS and Symmetra Power Array only. Puts the
UPS in Bypass mode and returns the UPS from Bypass
mode.
--------------------- CONTROL MENU ----------------------
1- Turn UPS ON
2- Turn UPS OFF
?- Help
>