7

3.5 Configure Call-UPS II

Call-

UPS II

requires on-site configuration before remote operation. You

will be able to change any of the settings later by the remote connection.
Follow these steps to configure Call-

UPS II

for:

Communication parameters

Password protection

Time and date

Paging (optional)

Dial-back security (optional)

Event logging (optional)

Initial Logging On

Connect

DTE

equipment (a dumb terminal or a computer running termi-

nal emulation software) to the Management Port of Call-

UPS II

using the

supplied null modem cable. It may be necessary to use an adapter (not
supplied) to connect the

DTE

equipment to the null modem cable.

Set the communication parameters of the DTE equipment to

9600

bits per

second, 8 data bits, no parity, and 1 stop bit (

9600

,

8, N, 1

).

With Call-

UPS II

running (Status Indicator on steady), press

CTRL

+

P

(press and hold the

CTRL

key while pressing the

P

key). At the prompt:

Enter Password>

Type in APC and press

ENTER

.

Note:

APC

is the factory default password for Call-

UPS II

. If the

default has been changed through previous configuration,
enter the changed password. Call-

UPS II

communication is

case sensitive. Enter

APC

in upper case.

On correct entry of the password, Call-

UPS II

displays the following

information:

---------------------- SMART-UPS 700 --------------------

Call-UPS II by American Power Conversion Corp
(c) Copyright 1994,95,97 All Rights Reserved

Site ID: 12345678
Location: Physical Location of This UPS

Press Any Key To Continue...