5 Problem Resolution

5.1 Troubleshooting Chart

TROUBLESHOOTING

Problem

Possible Cause

Solution

Power light flashes
rapidly when unit
is first turned on.

Internal problem with
Call-UPS II.

Disconnect Call-UPS II from
the UPS momentarily, then
reconnect.

Remote modem
will not answer.

Call-UPS II Setup item
Answer Ring set to 0.

Set Answer Ring to value other
th an 0 (ee Sec. 4.6).

Answer Lockout in
progress.

Call back after Answer Lockout
in terval has expired.

Remote modem plugged
into UPS that has been
turned off.

Plug remote modem into a wall
socket or use modem powered
by Call-UPS II.

Modem did not receive
setup string from Call-
UPS II.

Turn modem on before plugging
in Call-UPS II; check the cables.

Cannot log in
locally to con-
figure Call-UPS II.

Call-UPS II is dialing
back.

Press

ESC

to bypass the dialback

in progress or type

con nect

and

press

ENTER

. Call-UP S II will not

echo this message, so typing
will be “blind.”

Pages are not
getting through.

No @ symbol at the end
of the dial string.

Add an @ sy mbol at the end of
the dial strings in the Paging
Setup Menu. Many paging
controllers need additional time
to establish a connection.

Not enough time
between repeats, or not
enough repeats.

Add to the values in the Repeat
1, Repeat 2, and Paging Timer
settings in Paging Setup.

Call-UPS II is dialing
too quickly for the
paging equipment.

Set Dial Speed in Paging Setup
to a lower value.

Space character cancels
sending the page.

Set Space Character in Paging
Setup to none.