4.4 UPS Characteristics

UPS

characteristics are set at the factory for normal operation and usually

do not need to be changed. However if a change is needed, select items
from the

UPS

Characteristics menu. New settings may conflict with the

operation of UPS monitoring software in use, so check the requirements
of the system before changing them. Default and optional values for these
settings vary from one UPS to another.

Note: Smart-

UPS

products with serial numbers beginning with

the letter W do not support reporting and setting

UPS

characteristics with Call-

UPS II

. In this case, item 3,

UPS

Characteristics will not appear on the Main menu.

To display or change the characteristics of the

UPS

, type 3 and press

ENTER

from the Main menu. The appearance of the

UPS

Characteristics

menu will vary according to the type of the connected

UPS

. Refer to the

appropriate sections and accompanying tables that follow.

With Smart-UPS and Matrix-UPS

Call-

UPS II

connected to a Smart-

UPS

or Matrix-

UPS

displays the follow-

ing UPS Characteristics menu:

------------------- UPS CHARACTERISTICS -----------------

UPS ID: UPS_IDEN

1- Output: 240 V
2- Output Freq Range: AUTO
3- Output Voltage Reporting base: Auto
4- If UPS fails and freq or voltage is out of

range: Go to Bypass

---------------------------------------------------------

5- Low Battery Duration: 02 min.
6- Shutdown Delay: 020 sec.
7- Return Delay: 000 sec.
8- Return Battery Capacity: 00 %
9- Scheduled Self Test: every 14 Days

---------------------------------------------------------

10- Alarm if runtime is less than: 000 min.
11- Alarm if load is greater than: 00.0 kVA
12- Alarm if redundancy is less than: n+2 (0=never)

---------------------------------------------------------

13- Reset UPS to Default Settings

?- Help

Display Menu

Return to Previous Menu

>