Any changes to Call-

UPS II

communication settings are held until the end

of the session. Changes are made when Call-

UPS II

issues modem com-

mands at that time.

Connect to Modem

Call-

UPS II

requires a modem for remote

UPS

control and paging. If a

modem is used with Call-

UPS II

, some thought must be given to powering

it. Plugging the modem into the protected power output of the

UPS

will

keep the modem operating in bad power conditions, but remote turn-on
of the

UPS

will not be possible since, when the

UPS

is off, the modem

is off. By plugging the modem into a wall socket, remote turn-on of the

UPS

will work, but the modem will have to get by with unprotected

power. Also, it is possible in this situation to miss pages, since the
modem would be off in a power outage that Call-

UPS II

tries to report by

paging.

A better option is to use a modem designed for portable computers that
draws power from the computer. Call-

UPS II

will power such a modem,

providing protected power whether the

UPS

is on or off. Be careful to use

a modem that draws power from Call-

UPS II

, not a battery.

The configuration is complete. Disconnect the management device from
Call-

UPS II

. Connect the Call-

UPS II

according to the appropriate system

connection diagram on the following page.