Horner APG SmartStack I/O HE-RTD100* User Manual
Page 3
MAN0236-09
10 NOV 2006
PAGE 3
RTD000/100
This Data Sheet is published individually & also as a part of the SmartStack Supplement (SUP0246-05).
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
Digital Filtering. The illustration above demonstrates the effect of digital filtering (set with Filter
Constant) on module response to a temperature change.
4 TEMPERATURE
CONVERSION
For a given module configuration, use the appropriate formula in the table to obtain the actual
temperature (
°C or °F) that is represented by the value in the %AI register.
Temperature Conversion
Module
Configuration
Celsius Fahrenheit
0.05
°
°C = %AI / 20
°F = %AI / 20
0.1
°
°C = %AI / 10
°F = %AI / 10
0.5
°
°C = %AI / 2
°F = %AI / 2
750ms
20
1250ms
500ms
1000ms
250ms
0
0
10
100
90
80
70
60
50
40
30
Scans
1
2
3
4
5
6
7
0
Filter
Constant
%
C
om
pl
et
e [
]