PAGE 6
15 JAN 2010
MAN0432-04
Table 5
– LED Description
LED
RCS
RUN
•
OFF indicates OCS is in IDLE/STOP mode.
•
Flashing at 1 Hz indicates DO / IO mode or RUN with no ladder program.
•
ON indicates ladder code running.
OK
•
OFF indicates one or more self-tests failed.
•
Flashing at 1 Hz indicates I/O forcing is active.
•
ON indicates all self-tests passed.
Module Status (MS)
MS monitors RS-232 activity
•
OFF indicates no RS-232 communication.
•
Red flickering indicates receive activity on the RS-232 port.
•
Green flickering indicates transmit activity on the RS-232 port.
•
Orange flickering indicates both transmit and receive activity on the RS-
232 port.
•
Red solid ON indicates a non-critical self-test error was detected
•
Red flashing at 1Hz indicates a critical self-test error was detected.
Network Status (NS)
NS monitors CAN port
activity
•
OFF indicates no CAN communication.
•
Red flickering indicates receive activity on the CAN port.
•
Green flickering indicates transmit activity on the CAN port.
•
Orange flickering indicates both transmit and receive activity on the CAN
port.
•
Red solid ON indicates a CAN network error was detected.
4
SAFETY
All applicable codes and standards need to be followed in the installation of this product.
5
TECHNICAL ASSISTANCE
For updates and assistance, contact Technical Support at the following locations.
North America:
(317) 916-4274
www.heapg.com
Europe:
(+) 353-21-4321-266
www.horner-apg.com