Horner APG RCX HE500OCX510 User Manual
Mini ocs/rcs, Mixed i/o module, 1specifications
![background image](/manuals/414276/1/background.png)
OCX510
10 MAR 2003
PAGE 1
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
1
SPECIFICATIONS
INPUT
Inputs per Module
16 isolated
Minimum ON Current
1mA
Isolated Commons
per Module
3
Maximum OFF Current
200
µ
A
Input Voltage Range
12/24VDC
OFF to ON Response
1ms.
Peak Voltage
35VDC Max.
ON to OFF Response
1ms.
ON Voltage level
Min. 9VDC
OFF Voltage level
Max. 3VDC
Input Impedance
> 10K Ohms
Isolation between
Common and Ground
500VDC
OUTPUT
Outputs per Module
12 relay
Maximum Load current
(resistive) per
output
3A
Isolated Commons
per Module
4
Maximum Inrush Current
5A
Output Type
Relay
Minimum Load
None
Coil Voltage
20-28VDC
Isolation (Channel to
Channel and Channel to
Common)
500VDC
Contact Voltage
250VAC / 30VDC Max.
Maximum Leakage
Current
5
µ
A
ON Voltage drop
0.2V Max.
General Specifications
Required Power
(Steady State)
230mA @ 24VDC
UL
Required Power (Inrush)
770 mA @ 10ms.,
24VDC
CE
Please refer to Compliance Table located at
http://www.heapg.com/Support/compliance.htm
Relative Humidity
5 to 95%
Non-condensing
Terminal
Type
Spring Clamp, Removable
Operating Temperature
0
°
to 50
°
Celsius
Weight
9.5 oz. (270 g)
MAN0574-01
Mixed I/O Module
HE500OCX510
12/24 Vdc In, Positive/Negative Logic
3A Relay Out