beautypg.com

Horner APG XL6 OCS HEXT351C115 User Manual

Page 7

background image

MAN0887-05-EN

Specifications / Installation

__________________________________________________________________________________________________________________________________________________________________

3/2/2010

Page 7 of 8 #1037


6

I/O Register Map

Registers

Description

%I1 to %I24

Digital Inputs

%I32

Output Fault

%I25 to %I31

Reserved

%Q1 to %Q16

Digital outputs

%Q17

Clear HSC1 accumulator to 0

%Q18

Totalizer: Clear HSC2

Quadrature 1-2: Accumulator 1 Reset to

max – 1

%Q19

Clear HSC3 Accumulator to 0

%Q20

Totalizer: Clear HSC4

Quadrature 3-4: Accumulator 3 Reset to

max – 1

%Q21 to %Q32

Reserved

%AI1 to %AI4

Analog inputs

%AI5, %AI6

HSC1 Accumulator

%AI7, %AI8

HSC2 Accumulator

%AI9, %AI10

HSC3 Accumulator

%AI11, %AI12

HSC4 Accumulator

%AQ1, %AQ2

PWM1 Duty Cycle

%AQ3, %AQ4

PWM2 Duty Cycle

%AQ5, %AQ6

PWM Prescale

%AQ7, %AQ8

PWM Period

%AQ9 to %AQ14

Analog outputs

Note: Not all XL6 units contain the I/O listed in this table.

Registers

PWM

HSC

Stepper

%AQ1

Start Frequency

%AQ2

PWM1 Duty Cycle

(32 bit)

HSC1

Preset

Value

Run Frequency

%AQ3

%AQ4

PWM2 Duty Cycle

(32 bit)

HSC2

Preset

Value

Accel Count (32

bit)

%AQ5
%AQ6

PWM Prescale

(32 bit)

Run Count (32

bit)

%AQ7
%AQ8

PWM Period

(32 bit)

Decel Count (32

bit)

%Q1

Run

%I30

Ready/Done

%I31

Error


7

Digital Filtering for Analog Inputs


The digital filter is updated once per conversion. It is an “IIR” running average filter that emulates a simple
RC filter. The equivalent time constant is determined by the Filter Constant and the sum of the conversion
times for the two channels. The Filter Constant determines the weight given to the most recent
conversion. The following table lists the equivalent time constant for the three possible total conversion
times, which are dependent upon the two input mode selections. This filter delay is in addition to the PLC
scan delay.


Equivalent RC Time Constant in Seconds

(Nominal time to reach 63% of final value.)

Total Conversion Time in Seconds

Filter Constant

0.03

0.09

0.13

0*

0.03*

0.09*

0.13*

1

0.07

0.18

0.27

2

0.13

0.35

0.53

3

0.27

0.71

1.07

4

0.53

1.41

2.13

5

1.07

2.83

4.27

6

2.14

5.65

8.54

7

4.28

11.30

17.08

* No filter delay, reading is unfiltered conversion value



8

Thermocouple Grounding Schemes



































Ungrounded Thermocouples

Alternate Shield Connection for

Ungrounded Thermocouples.

Ungrounded Thermocouples

Preferred Shield Connection for

Ungrounded Thermocouples.

Grounded Thermocouples

Field Ground Potential Less Than

Seven Volts AC

Typical Shield Connection for

Grounded Thermocouples

Grounded Thermocouples

Field Ground Potential Less Than

Seven Volts AC

Shields Connected at One End Only

May be Used to Reduce Noise

Grounded Thermocouples May Use

the Ungrounded Thermocouple Shield

Connections if the Shield is not

Grounded at the Field End

Note: The examples for thermocouple grounding schemes above are generic illustrations. The

XL6 model XL105 has two thermocouple inputs.