beautypg.com

Horner APG XL6 OCS HEXT351C112 User Manual

Page 4

background image

MAN0885-04-EN

Specifications / Installation

__________________________________________________________________________________________________________________________________________________________________

3/2/2010 Page 4 of 6 #1037

























4.2

External DIP Switch Settings




















MJ2 Pinouts in Half and Full Duplex Modes


Table - Ports and Functions

Functions

Port 1 (MJ1)

Port 2 (MJ2)

RS-232

Hardware Handshaking

X

Programming

X

Ladder function
controlled

Serial Downloable
Protocols

RS 485 Full duplex

X

RS485 Half duplex

NET1 Port Pin Assignments

Pin

Signal

Signal Description

Direction

1

V-

CAN Ground

2

CN_L

CAN Data Low

In/Out

3

SHLD

Shield Ground

4

CN_H

CAN Data High

In/Out

5

NC

No Connect

Speeds

10 BaseT Ethernet (10-Mbps)

100 BaseTx Fast Ethernet (100-Mbps)

Modes

Half or Full Duplex

Auto-Negotiation

Both 10/100-Mbps and Half/Full Duplex

Connector Type

Shielded RJ-45

Cable Type
(Recommended)

CAT5 (or better) UTP

Port

Auto MDI/MDI-X

4.1

Serial Communications:


MJ1: (RS-232 / RS-485) Use for Cscape programming

and Application-Defined Communications.


MJ2: (RS-232 / RS-485) Use for Application-Defined

Communications.

As seen when looking at the side of the XL6 unit :


The DIP Switches are used for
termination of the RS-485 ports. The
XL6 is shipped un-terminated.


To terminate, select one of the DIP
Switches and configure it based upon
the option that is desired.

Pin

MJ1 Pins

MJ2 Pins

Signal

Direction

Signal

Direction

8

TXD

OUT

TXD

OUT

7

RXD

IN

RXD

IN

6

0 V

Ground

0 V

Ground

5*

+5 60mA

OUT

+5 60mA

OUT

4

RTS

OUT

TX-

OUT

3

CTS

IN

TX+

OUT

2

RX- / TX-

IN / OUT

RX-

IN

1

RX+ / TX+

IN / OUT

RX+

IN

1

8




SW1 -

ON enables MJ2 RS485 port termination (121 Ohms).

OFF disables MJ2 RS485 port termination.


SW2 & SW3 - ON places MJ2 RS485 port in half-duplex mode.

OFF places MJ2 RS485 port in full-duplex mode.


SW4 -

ON enables MJ1 RS485 port termination (121 Ohms).

OFF disables MJ1 RS485 port termination.

MJ1

MJ2

On

Off

On

Off

On

Off

CAN Connector

Use the CAN Connector when using CsCAN network.

Torque rating 4.5 – 7 Lb-In

(0.50 – 0.78 N-m)

4.3

CAN Network Port and Wiring


4.4

Ethernet Port


* +5V 60mA Max

MJ2 Half Duplex Mode

Pin

MJ2 Pins

Signal

Direction

8

TXD

OUT

7

RXD

IN

6

0 V

Ground

5*

+5 60mA

OUT

4

TX-

OUT

3

TX+

OUT

2

TX-/RX-

IN/OUT

1

TX+/RX+

IN/OUT

1

8

Pin

MJ2 Pins

Signal

Direction

8

TXD

OUT

7

RXD

IN

6

0 V

Ground

5*

+5 60mA

OUT

4

TX-

OUT

3

TX+

OUT

2

RX-

IN

1

RX+

IN

1

8

* +5V 60mA Max

MJ2 Full Duplex Mode