Horner APG XL6 OCS HEXT351C112 User Manual
Page 2
MAN0885-04-EN
Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________
3/2/2010 Page 2 of 6 #1037
2
Installation
1. Prior to mounting, observe requirements for the panel layout design
and spacing/clearances in the OCS XL6 Series Manual (MAN0883).
2. Cut the host panel.
3. Insert the OCS through the panel cutout (from the front). The gasket
material needs to be between the host panel and the OCS.
4. Install and tighten the mounting clips (provided with the OCS) until the
gasket material forms a tight seal.
5. Connect cables as needed such as communications, programming,
power and CsCAN cables to the ports using the provided connectors.
6. Begin configuration procedures.
3
Panel Cut-Out and Dimensions
Refer to the XL6 User Manual (MAN0883) for panel box information and a handy checklist of requirements.
Note: The tolerance to meet NEMA standards is
±
0.005” (0.1 mm).
Caution: Do not force the OCS into the panel cutout.
An incorrectly sized panel cutout can damage the
touch screen.
Note: Max. panel thickness: 5 mm
001XLQX007
6.875”
[175mm]
[131mm]
001OCS003-R1
5.156”
R .125” [3 mm] TYP.
RADIUS CORNERS
WHEN REQUIRING
DUST OR WATER
TIGHT SEAL PER
NEMA 4, 4X OR 12