The Security Code determines the programming mode and the accessibility

of programming parameters. This code can be used along with the Program

Mode Lock-out (

P-Loc

) in the User Input Function parameter (Module 1).

Two programming modes are available. Full Programming mode allows all

parameters to be viewed and modified. Quick Programming mode permits only

the Setpoint values to be modified, but allows direct access to these values

without having to enter Full Programming mode.

Programming a Security Code other than 0, requires this code to be entered

at the

CodE

prompt in order to access Full Programming mode. Depending on

the code value, Quick Programming may be accessible before the

CodE

prompt

appears (see chart).

PROGRAMMING SECURITY CODE

000

to

999

000

CodE

USER INPUT

FUNCTION

USER INPUT

STATE

SECURITY

CODE

MODE WHEN “PAR”

BUTTON IS PRESSED

FULL PROGRAMMING

MODE ACCESS

0

Full Programming

Immediate Access

not

P-Loc

______

1-99

Quick Programming

After Quick Programming

with correct code entry

at

CodE

prompt *

100-999

CodE

prompt

With correct code entry

at

CodE

prompt *

0

Programming Lock

No Access

Active

1-99

Quick Programming

No Access

P-Loc

100-999

CodE

prompt

With correct code entry

at

CodE

prompt *

Not Active

0-999

Full Programming

Immediate Access

5.4 Module 4 - s

etpoInt

o

utput

p

araMeters

(

4-SPt

)

PAR

Pro

Enb-n

Setpoint

Action

Setpoint

Select

Setpoint

Value

Output Reset

Action

Hysteresis

Value

Off Time

Delay

On Time

Delay

Output Reset

W/Display

Reset

SPSEL

4-SPt

Act-n

SPt-n

HYS-n

tON-n

tOF-n

rSt-n

rEn-n

Standby

Operation

Stb-n

Setpoint

Enable

PARAMETER MENU

OUTPUT

STATE

OFF

ON

Hys

SP + Hys

SP

OFF

TRIGGER POINTS

Low Acting (Unbalanced Hys) =

LO-Ub

OUTPUT

STATE

OFF

ON

Hys

SP

SP - Hys

OFF

TRIGGER POINTS

High Acting (Unbalanced Hys) =

HI-Ub

Enter the setpoint (output) to be programmed. The

n

in the following

parameters will reflect the chosen setpoint number. After the chosen setpoint

is completely programmed, the display will return to

SPSEL

. Repeat steps for

each setpoint to be programmed. Select

NO

to exit the module.

SETPOINT SELECT

NO

SPSEL

NO

SP-1

SP-2

Select

YES

to enable Setpoint

n

and access the setup parameters. If

NO

is

selected, the unit returns to

SPSEL

and Setpoint

n

is disabled.

SETPOINT ENABLE

NO

Enb-n

YES

NO

Enter the action for the selected setpoint (output). See Setpoint Output

Figures for a visual detail of each action.

SETPOINT ACTION

HI-Ub

Act-n

HI-bL

LO-bL

HI-Ub

LO-Ub

High Acting, with balanced hysteresis
Low Acting, with balanced hysteresis
High Acting, with unbalanced hysteresis
Low Acting, with unbalanced hysteresis

=

HI-bL

=

LO-bL

=

HI-Ub

=

LO-Ub

OUTPUT

STATE

OFF

ON

Hys

SP + ½Hys

SP

SP - ½Hys

OFF

TRIGGER POINTS

High Acting (Balanced Hys) =

HI-bL

OUTPUT

STATE

OFF

ON

Hys

SP + ½Hys

SP

SP - ½Hys

OFF

TRIGGER POINTS

Low Acting (Balanced Hys) =

LO-bL

SETPOINT VALUE

Enter the desired setpoint value. The decimal point position for the setpoint

and hysteresis values follow the selection set in Module 1.

-19999

to

99999

001.00

SPt-n

2

HYS-n

HYSTERESIS VALUE

1

to

59999

Enter desired hysteresis value. See Setpoint Output Figures for visual

explanation of how setpoint output actions (balanced and unbalanced) are

affected by the hysteresis. When the setpoint is a control output, usually

balanced hysteresis is used. For alarm applications, usually unbalanced

hysteresis is used. For unbalanced hysteresis modes, the hysteresis functions on

the low side for high acting setpoints and functions on the high side for low

acting setpoints.
Note: Hysteresis eliminates output chatter at the switch point, while time delay

can be used to prevent false triggering during process transient events.

* Entering Code 222 allows access regardless of security code.