No usrin, Dsp u-asn, Lo u-act – Red Lion PAXLA User Manual
Page 7: No lo-en, No fcs, 0 lo-t, 66 code, 50 code, 0 hi-t, No hi-en

7
USER INPUT ASSIGNMENT
Select the value(s) to which the User Input Function is assigned. The User
Input Assignment only applies if a selection of reset, or display hold is selected
in the User Input Function menu.
MODE
DISPLAY
No Function
NO
DESCRIPTION
User Input disabled.
Program Mode Lock-out
P-Loc
Zero Input
(Edge triggered)
ZErO
Zero the Input Display value causing
Display Reading to be Offset.
d-SEL
d-LEV
d-HLd
rESEt
Resets the assigned value(s) to the current
input value.
HI-LO
HI
dSP
LO
See Programming Mode Access chart
(Module 3).
Setpoint 1 and 2 Reset
Setpoint 1 Reset
Setpoint 2 Reset
Reset both setpoint 1 and 2 outputs.
Resets setpoint 1 output.
Resets setpoint 2 output.
rSt12
rSt-1
rSt-2
USER INPUT FUNCTION
NO
USrIN
dSP
U-ASN
Display Select
(Edge Triggered)
Display Intensity Level
(Edge Triggered)
Display Hold
Reset (Edge triggered)
Advance once for each activation.
Increase intensity one level for each
activation.
Holds the assigned display, but all other
meter functions continue as long as
activated (maintained action).
LO
U-Act
USER INPUT ACTIVE LEVEL
Select whether the user input is configured as active low or active high.
LO
HI
Entering Code 66 will overwrite all user settings with
the factory settings. The meter will display
rESEt
and then
return to
CodE 00
. Press the
PAR
button to exit the
module.
MIN DISPLAY ENABLE
YES
NO
NO
LO-En
NO
FCS
2.0
LO-t
MIN CAPTURE DELAY TIME
When the Input Display is below the present MIN value for the entered delay
time, the meter will capture that display value as the new MIN reading. A delay
time helps to avoid false captures of sudden short spikes.
0.0
to
999.9
sec.
Select
yES
to perform any of the Factory Service Operations shown below.
FACTORY SERVICE OPERATIONS
yES
NO
Enables the Minimum Display Capture capability.
The PAXLA uses stored calibration values to provide
accurate measurements. Over time, the electrical
characteristics of the components inside the PAXLA will
slowly change with the result that the stored calibration
values no longer accurately define the input circuit. For
most applications, recalibration every 1 to 2 years should be sufficient.
Calibration of the PAXLA involves a calibration which should only be
performed by individuals experienced in calibrating electronic equipment. Allow
30 minute warm up before performing any calibration related procedure. The
following procedures should be performed at an ambient temperature of 15 to 35
°C (59 to 95 °F).
CAUTION: The accuracy of the calibration equipment will directly affect the
accuracy of the PAXLA.
CALIBRATION
66
CodE
RESTORE FACTORY DEFAULT SETTINGS
Entering Code 50 will display the version (x.x) of the
meter. The display then returns to CodE 00. Press the
PAR
button to exit the module.
50
CodE
VIEW MODEL AND VERSION DISPLAY
48
CodE
5.2 Module 2 - s
econdary
F
unctIon
p
araMeters
(
2-SEC
)
PAR
Max Capture
Delay Time
Max Display
Enable
Min Display
Enable
Access Code
For Service
Operations
Min Capture
Delay TIme
Factory
Service
Operations
2-SEC
HI-En
HI-t
LO-En
LO-t
FCS
CodE
Pro
PARAMETER MENU
2.0
HI-t
MAX CAPTURE DELAY TIME
When the Input Display is above the present MAX value for the entered
delay time, the meter will capture that display value as the new MAX reading.
A delay time helps to avoid false captures of sudden short spikes.
0.0
to
999.9
sec.
NO
HI-En
MAX DISPLAY ENABLE
YES
NO
Enables the Maximum Display Capture capability.