0.0
tOF-n
OFF TIME DELAY
0.0
to
599.9
Sec
Enter the time value in seconds that the output is delayed from turning off
after the trigger point is reached. A value of 0.0 allows the meter to update the
output status per the response time listed in the Specifications.
Enter the reset action of the output. See figure for details.
Auto
= Automatic action; This action allows the output to automatically reset
off at the trigger points per the Setpoint Action shown in Setpoint Output
Figures. The “on” output may be manually reset (off) immediately by the
front panel
RST
button or user input.The output remains off until the trigger
point is crossed again.
LAtCH
= Latch with immediate reset action; This action latches the output on at
the trigger point per the Setpoint Action shown in Setpoint Output Figures.
Latch means that the output can only be turned off by the front panel
RST
button or user input manual reset, or meter power cycle. When the user input
or
RST
button is activated (momentary action), the corresponding “on” output
is reset immediately and remains off until the trigger point is crossed again.
(Previously latched alarms will be off if power up Display Value is lower than
setpoint value.)
L-dLY
= Latch with delay reset action; This action latches the output on at the
trigger point per the Setpoint Action shown in Setpoint Output Figures. Latch
means that the output can only be turned off by the front panel
RST
button or
user input manual reset, or meter power cycle. When the user input or
RST
button is activated (momentary action), the meter delays the event until the
corresponding “on” output crosses the trigger off point. (Previously latched
outputs are off if power up Display Value is lower than setpoint value. During
a power cycle, the meter erases a previous
L-dLY
reset if it is not activated at
power up.)
OUTPUT RESET ACTION
LAtCH
Auto
L-dLY
Auto
rSt-n
OUTPUT
STATE
OFF
ON
Hys
SP
Auto
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
MANUAL
RESET
LAtCH
L-dLY
SP - Hys
( )
( )
( )
{
Setpoint Output Reset Actions
This parameter enables the
RST
button or user input to reset the output when
the display is reset.
Note: For this parameter to operate, the
RST
button or User Input being used
must be set to
dSP
and the Input value must be displayed. If these conditions
are not met, the output will not reset.
YES
rEn-n
OUTPUT RESET WITH DISPLAY RESET
YES
NO
When
YES
, the output is disabled (after a power up) until the trigger point is
crossed. Once the output is on, the output operates normally per the Setpoint
Action and Output Reset Action.
NO
Stb-n
STANDBY OPERATION
YES
NO
0.0
tON-n
ON TIME DELAY
Enter the time value in seconds that the output is delayed from turning on
after the trigger point is reached. A value of 0.0 allows the meter to update the
output status per the response time listed in the Specifications.
0.0
to
599.9
Sec