0 tof-n, Auto rst-n, Yes ren-n – Red Lion PAXLA User Manual

Page 10: No stb-n, 0 ton-n

background image

10

0.0

tOF-n

OFF TIME DELAY

0.0

to

599.9

Sec

Enter the time value in seconds that the output is delayed from turning off

after the trigger point is reached. A value of 0.0 allows the meter to update the

output status per the response time listed in the Specifications.

Enter the reset action of the output. See figure for details.

Auto

= Automatic action; This action allows the output to automatically reset

off at the trigger points per the Setpoint Action shown in Setpoint Output

Figures. The “on” output may be manually reset (off) immediately by the

front panel

RST

button or user input.The output remains off until the trigger

point is crossed again.

LAtCH

= Latch with immediate reset action; This action latches the output on at

the trigger point per the Setpoint Action shown in Setpoint Output Figures.

Latch means that the output can only be turned off by the front panel

RST

button or user input manual reset, or meter power cycle. When the user input

or

RST

button is activated (momentary action), the corresponding “on” output

is reset immediately and remains off until the trigger point is crossed again.

(Previously latched alarms will be off if power up Display Value is lower than

setpoint value.)

L-dLY

= Latch with delay reset action; This action latches the output on at the

trigger point per the Setpoint Action shown in Setpoint Output Figures. Latch

means that the output can only be turned off by the front panel

RST

button or

user input manual reset, or meter power cycle. When the user input or

RST

button is activated (momentary action), the meter delays the event until the

corresponding “on” output crosses the trigger off point. (Previously latched

outputs are off if power up Display Value is lower than setpoint value. During

a power cycle, the meter erases a previous

L-dLY

reset if it is not activated at

power up.)

OUTPUT RESET ACTION

LAtCH

Auto

L-dLY

Auto

rSt-n

OUTPUT

STATE

OFF

ON

Hys

SP

Auto

OFF

ON

OFF

OFF

ON

OFF

ON

OFF

OFF

ON

OFF

ON

OFF

MANUAL

RESET

LAtCH

L-dLY

SP - Hys

( )

( )

( )

{

Setpoint Output Reset Actions

This parameter enables the

RST

button or user input to reset the output when

the display is reset.

Note: For this parameter to operate, the

RST

button or User Input being used

must be set to

dSP

and the Input value must be displayed. If these conditions

are not met, the output will not reset.

YES

rEn-n

OUTPUT RESET WITH DISPLAY RESET

YES

NO

When

YES

, the output is disabled (after a power up) until the trigger point is

crossed. Once the output is on, the output operates normally per the Setpoint

Action and Output Reset Action.

NO

Stb-n

STANDBY OPERATION

YES

NO

0.0

tON-n

ON TIME DELAY

Enter the time value in seconds that the output is delayed from turning on

after the trigger point is reached. A value of 0.0 allows the meter to update the

output status per the response time listed in the Specifications.

0.0

to

599.9

Sec