beautypg.com

Red Lion PAXLCR User Manual

Page 7

background image

COUNTER RESET AT POWER-UP





COUNTER B SCALE FACTOR

The number of input or batch counts is multiplied by the scale factor to

obtain the desired process value. A scale factor of 1.0000 will result in the
display of the actual number of input or batch counts. (Details on scaling
calculations are explained at the end of this section.)*



to











SCALING FOR COUNT INDICATION

The counter’s scale factor is factory set to 1, to provide one count on the

display for each pulse that is input to the unit. In many applications, there will
not be a one-to-one correspondence between input pulses and display units.
Therefore, it is necessary for the meter to scale or multiply the input pulses by
a scale factor to achieve the desired display units (feet, meters, gallons, etc.)

The Count Scale Factor Value can range from 00.0001 to 99.9999. It is

important to note that the precision of a counter application cannot be improved
by using a scale factor greater than one. To accomplish greater precision, more
pulse information must be generated per measuring unit. The following formula
is used to calculate the scale factor.

Scale Factor = Desired Display Units x Decimal Point Position

Number of Pulses

WHERE:
Desired Display Units
: Count display units acquired after pulses that occurred.

Number of Pulses: Number of pulses required to achieve the desired

display units.

Decimal Point Position:

0 =

1

0.0 =

10

0.00 = 100
0.000 = 1000
0.0000 = 10000
0.00000 =

100000

EXAMPLE 1: The counter display is used to indicate the total number of feet

used in a process. It is necessary to know the number of pulses for the
desired units to be displayed. The decimal point is selected to show the
resolution in hundredths.

Scale Factor =

Desired Display Units x Decimal Point Position

Number of Pulses

Given that 128 pulses are equal to 1 foot, display total feet with a one-

hundredth resolution.

Scale Factor =

1.00 x 100

128
Scale Factor = 0.007812 x 100
Scale Factor = 0.7812

EXAMPLE 2: A manufacturer wants to count the total number of bricks

molded in a process yielding 12 bricks per mold. The counter receives 1
pulse per mold and should increase by 12 for each pulse received. Since
single brick accuracy is not required, a Scale Factor greater than 1 can be
used in this case.

Scale Factor =

Desired Display Units x Decimal Point Position

Number of Pulses

Scale Factor =

12 x 1

1
Scale Factor = 12.0000

*For value entry instructions, refer to selection/value entry in the Programming

The Meter section.









USER INPUT ASSIGNMENT

The User Input Assignment is only active when Counter B is enabled and the

user input selection performs a Reset, Inhibit or Store function on one or both
of the counters.

USER INPUT FUNCTION

MODE

DISPLAY

No Function



DESCRIPTION

User Input disabled.

Program Mode Lock-out



Maintained Reset

Inhibit





Level active reset of the
selected counter(s).

Inhibit counting for the
selected counter(s).

Store



Store and Reset













Edge triggered reset of the
selected counter(s) after
storing the count.







See Programming Mode
Access chart (Module 3).

Setpoint 1 and 2 Reset *

Setpoint 2 Reset *

Setpoint 1 Reset *

Display Intensity Level *

Display Select *

Freeze display for the selected
counter(s) while allowing
counts to accumulate internally.

Reset both setpoint 1 and 2
outputs.

Reset setpoint 2 output.

Reset setpoint 1 output.

Increase intensity one level
for each activation.

Advance once for each
activation.













7

USER INPUT ACTIVE LEVEL

Select whether the user input is configured as active low or active high.





The selected counter(s) will reset at each meter power-up.

* Indicates Edge Triggered function. All others are Level Active functions.