3.3 USER INPUT WIRING

CAUTION: DC common (Terminal 4) is NOT isolated from Input common (Terminal 7) or User common (Terminal 9). In order

to preserve the safety of the meter application, DC common must be suitably isolated from hazardous live earth referenced
voltage; or Input common and User common must be at protective earth ground potential. If not, hazardous voltage may be
present at the Signal or User Inputs, and Input or User common terminals. Appropriate considerations must then be given
to the potential of the Input or User common with respect to earth ground.

Terminal 8: User Input

Terminal 9: User Common

3.4 SETPOINT (OUTPUT) WIRING

Terminal 10: NC 1

Terminal 11: NO 1

Terminal 12: Relay 1 Common

Terminal 13: NC 2

Terminal 14: NO 2

Terminal 15: Relay 2 Common

USER INPUT

8

USER COMMON

9

USER INPUT

USER COMMMON

9

8

+

-

10 N.C. 1

COMM 1

12

11 N.O. 1

13

14

15

N.C. 2

N.O. 2

COMM 2

Current Sinking (Active Low Logic)

Current Sourcing (Active High Logic)

3.2 INPUT SIGNAL WIRING

3.1 POWER WIRING

COMMON

+ 24V EXC

4

3

DC Out Power

Terminal 3: + 24 VDC OUT

Terminal 4: Common

Power

Terminal 1: VAC/DC +

Terminal 2: VAC/DC -

1

2

AC/DC

AC/DC

+

-

~

~

2

1

ON

3 4

*

MAGNETIC PICKUP

INPUT B

COMMON

INPUT A

COMMON

4

5

6

7

*

5

+24V EXC.

3

t 2 5

A MAX

Resistor to Limit Current

ON

1 2 3

*

4

*

AC

*

5

INPUT A

INPUT B

COMMON

7

6

5

+24V EXC.

COMMON

3

4

1 2

ON

3 4

* *

2.2 kΩ

*

5

INPUT A

INPUT B

COMMON

7

6

5

+24V EXC.

COMMON

3

4

2

1

ON

3 4

* *

O.C.

NPN

*

5

INPUT A

INPUT B

COMMON

7

6

5

+24V EXC.

COMMON

3

4

1 2 3

ON

*

4

*

O.C.

PNP

*

5

INPUT A

INPUT B

COMMON

7

6

5

+24V EXC.

COMMON

3

4

1 2 3 4

ON

*

COMMON

+5 V

*

5

INPUT A

INPUT B

COMMON

7

6

5

+24V EXC.

COMMON

3

4

2

1

ON

* *

3 4

*

5

INPUT A

INPUT B

COMMON

7

6

5

+24V EXC.

COMMON

3

4

*

1 2 3

ON

*

4

*

5

INPUT A

INPUT B

COMMON

7

6

5

+24V EXC.

COMMON

3

4

AC Inputs From Tach Generators, Etc.

Input A

Two Wire Proximity, Current Source

Input A

Magnetic Pickup

Input A

Current Sourcing Output

Input A

Interfacing With TTL

Input A

Current Sinking Output

Input A

Switch or Isolated Transistor; Current Sink

Input A

1 2 3 4

ON

5

INPUT A

INPUT B

COMMON

7

6

5

+24V EXC.

COMMON

3

4

Switch or Isolated Transistor; Current Source

Input A

*

Switch position is application dependent.

Current Sink Output; Quad/Direction

Shaded areas not recommended for counting applications.

The meter provides a choice of eight different count modes using two signal inputs,

A and B. The Count Mode selected determines the action of Inputs A and B. Section
5.1, Input Setup Parameters, provides details on count mode selection and input action.