PROGRAM USER MODULE (Cont’d)
SKIP PRESET 1 (SKIP P1)
Output 1 will NOT activate and an automatic reset will NOT occur
when the count value equals preset 1 if the user input is active. This
mode is typically used with the Automatic Reset at output 1 or output 2
mode, or the reset after timed output 1 or 2 mode. The skip preset 1 is
maintained.
PROGRAM DISABLE (PGM. DIS.)
Only one external User Input can be used for this option. This option
used with the Program Disable DIP switch can limit operator access to
programmable parameters (Refer to Operator Accessible Functions With
Program Disable section). The program disable is maintained.
PROGRAM OUTPUTS MODULE
Presets 1 and 2 activate solid state Outputs 1 and 2 respectively. The
outputs can be assigned to either the Count or Rate display and the
preset values will automatically be assigned to the appropriate display.
The relays operate in parallel with the solid state outputs on the optional
relay board. A manual reset will override a timed output. If boundary or
latched is selected for the output mode, the time value will not appear as
an option.
Program Output 2 has the same programmable options as Output 1,
except the “OUT1 END” Sub-menu will be “OUT2 END” and the
options are: DISABLED, @OUT1, @OUT1END. The following
flowchart shows only the Outputs portion:
PHASE
The positive (+) phase of an output indicates that when the display
value equals the preset value, the output will turn on. When the output is
reset it will be turned off.
A minus (-) phase mode refers to the complementing of the logic state of the
output. When the display value equals the preset value, the output will turn
off. The reset condition of the output is the on state. When an output is
changed to the other phase it will not take effect until a manual reset or power
down is performed.
Note: The state of the relay, if used, will be the same as the solid state output.
-20-