Technical data, Specifications, Performance (hmp60 and hmp63) – Vaisala HMP110 User Manual
Page 65: Relative humidity, Temperature, Dewpoint, Chapter 7, technical data, pr, Technical data on p, Chapter 7
Chapter 7 ____________________________________________________________ Technical Data
VAISALA _______________________________________________________________________ 63
CHAPTER 7
TECHNICAL DATA
This chapter provides the technical data of the HMP60 and HMP110
series probes.
Specifications
Performance (HMP60 and HMP63)
Relative Humidity
Measurement range
0 ... 100 %RH
Typical accuracy
temperature range +0 ... +40 °C
0 ... 90 %RH
±3 %RH
90 ... 100 %RH
±5 %RH
temperature range -40 ... 0 °C
and +40 ... +60 °C
0 ... 90 %RH
±5 %RH
90 ... 100 %RH
±7 %RH
Humidity sensor
Vaisala INTERCAP®
Temperature
Measurement range
-40 ... +60 °C
Accuracy over temperature range
+10 ... +30 °C
±0.5 °C
-40 ... +60 °C
±0.6 °C
Dewpoint
Measurement range
-40 ... +60 °C
Typical accuracy
temperature range 0 ... +40 °C
when dewpoint depression* < 15 °C
±2 °C
temperature range -40 ... 0 °C
and +40 ... +60 °C when
dewpoint depression* < 10 °C
±3 °C
*dewpoint depression = ambient temperature - dewpoint