Connect to the probe in poll mode, Close the connection in poll mode, Reset the probe – Vaisala HMP110 User Manual
Page 52: E 50

User's Guide ______________________________________________________________________
50 __________________________________________________________________ M211060EN-E
Connect to the Probe in POLL Mode
Use the OPEN command to connect to a probe that is in POLL mode.
OPEN [aa]
where
aa
=
address (0 ... 255)
Example:
open 1
HMP110 1 line opened for operator commands
Close the Connection in POLL Mode
The CLOSE command closes the connection to the probe.
CLOSE
Example:
close
line closed
Reset the Probe
Use the RESET command to reset the probe. Upon reset or power-up,
the probe enters the serial mode that has been set with the SMODE
command.
RESET
Example (probe set to serial mode STOP, will output probe model and
software version at reset):
reset
HMP60 / 1.00.0
Example (probe set to serial mode RUN, will start to output measurement
messages at reset):
reset
T= 23.6 'C RH= 20.2 %RH Td= -0.5 'C
T= 23.6 'C RH= 20.2 %RH Td= -0.5 'C
T= 23.3 'C RH= 20.2 %RH Td= -0.8 'C
...