The default value for the power save level slave

adjust only screen is 1. Press the or

soft keys to adjust this value. Press the

soft key to change the value of each Slave FX.

• The Slave(s) must be connected to Port 2 or

higher on the HUB.

• With the Master FX default value of zero in the

power save level master adjust only screen, all of

the Slave FX’s will remain OFF until the Master

FX needs help and calls for the Slave FXs with

“Slave Rank” equal to 1 to come ON.

• Choose a diff erent “Slave Rank” for each Slave

FX. This helps assure proper operation and

allows them to come ON one at a time saving

power in the long run. Otherwise, with a

default value of 1 for all Slaves, they will all

come on whenever a 12 amp load calls for

more power, but then can quickly shut off

because multiple FXs provide far more than

the required 12 amps. Ranking them 1, 2, 3, 4

etc. means they will come on one at a time as

needed to better serve the loads and conserve

energy.

ADV/FX/STACK------------P02

power save level 1

slave adjust only

DOWN INC DEC PORT

ADV/FX/STACK-----------------

stacking setup

completed

TOP ADV MAIN

Press the

soft key to return to the Main

Menu.

Press the soft key to view the fi nal

stacking screen.