Stacking and assigning fx status, 3-phase, 1-2ph master – Outback Power Systems VFX Series International Programming Manual User Manual

Page 25

background image

24

2. 3-Phase

• Three—and only three— FXs are connected, one to each of three 230 VAC output legs that produce

400 VAC between any two legs of the system.

• The HUB requires a jumper between the two Slave FXs for this stacking to function (see HUB

Communications Manager User’s Manual).

• The AC input source (generator or grid) must be a 230VAC/400VAC 3-phase source.

STACKING AND ASSIGNING FX STATUS

Use the MATE to establish the order or hierarchy of all the system FXs by designating each as one of

the following:

• 1-2ph Master (OutBack Parallel, OutBack Series, or Classic Series stacking)

• Classic Slave (Classic Series stacking)

• OB (OutBack) Slave L1 (OutBack Parallel, OutBack Series, or OutBack Series/Parallel stacking)

• OB (OutBack) Slave L2 (OutBack Series or OutBack Series/Parallel stacking)

• 3ph Master (3-Phase stacking)

• 3ph Slave (3-Phase stacking)

NOTE: Some stacking options that appear on the MATE should not be used with an International Series
FX or VFX and are marked as such in the text.

1. 1-2ph Master

• This is the default ranking of every FX. It applies to one-phase and two-phase systems.

• One Master FX is established for every multiple FX system.

*A&B

A&C
B&C

Any two

legs*

400 VAC

6kW

3 kW 230 VAC

LOAD

3-phase, all

three legs,

9kW

or

3 kW 230 VAC

3 kW 230 VAC

Phase B

230 VAC

3kW

Phase A

230 VAC

3kW

Phase C

230 VAC

3kW

or