beautypg.com

Introduction to power save levels – Outback Power Systems VFX Series International Programming Manual User Manual

Page 33

background image

32

INTRODUCTION TO POWER SAVE LEVELS

Depending on the model, each FX consumes 20-25 watts of power when it remains on, even if it isn’t

actively inverting or charging. OutBack Power Systems off ers the option to shut down (put into Silent

mode) some or all of the Slave FXs until the loads require them to come on again.

• When a load exceeds six amps AC, the Master FX shares the load with one or more Slave FXs.

• When the Master detects only a two amp load, a Slave FX goes into Silent mode; Slaves will continue

to go into Silent mode as long as the Master detects four amps.

The next two screens in the MATE’s Stack menu adjust the power levels of the Master and Slave FXs.

From any STACK PHASE screen:

• Press the soft key once to bring up the power save level master adjust only screen

• Press the soft key again to bring up the power save level slave adjust only screen

NOTE:

These power save level master adjust only and power save level slave adjust only screens

pertain to systems that have OB Slave L1 and/or OB Slave L2 type slaves only.

ADV/FX/STACK-------------P01

(ANY SCREEN IN STACK PHASE)

DOWN INC DEC PORT

Press the soft key once.

ADV/FX/STACK------------P01

power save level

master adjust only

DOWN INC DEC PORT

Press the soft key to increase the power

save level master adjust only value. Any Slave with

this value or lower, which is assigned in the

power save level slave adjust only screen (next),

will be on with the Master. If the power save

level master adjust only is three, for instance,

any Slave assigned a value of 3 or lower will be

on when the Master is on. Since the Master is

essentially always ON, these Slaves will always

be on as well. Any Slave with a value of 4 and

higher will be Silent until the Master activates

them for larger loads. For days of the week with

small load demands, a user can decrease the

power save level master adjust only value so

fewer FXs are running. The default value is zero

(only the Master is on).

Press to view the power save level slave

adjust only screen.