Outback Power Systems VFX Series International Programming Manual User Manual
Page 15
14
ADV/FX/CHARGER---------P00
absorb
01.0 hrs
time limit
DOWN INC DEC PORT
ADV/FX/CHARGER---------P00
fl oat 13.6 vdc
set point
DOWN INC DEC PORT
ADV/FX/CHARGER---------P00
fl oat 01.0 hrs
time period
DOWN INC DEC PORT
ADV/FX/CHARGER---------P00
refl oat 12.2vdc
set point
DOWN INC DEC PORT
The absorb time limit must be long enough for
the batteries to regain 95-100% of their charge.
This time limit can be set between 0 hours and 24
hours using
and . The FX auto-
matically reduces this limit when it’s connected to
a partially charged battery. Press
to con-
tinue in the CHARGER Menu.
The fl oat set point is the batteries’ fi nishing charge
which completes the recharging process. This
setting ranges from 12.0VDC to 15.0VDC. Press
to continue.
The fl oat time period is the amount of time—from
0 to 24 hours— the recharging process maintains
the fl oat set point. Larger batteries will probably
require more time than smaller batteries. The
recharging stops when the fl oat time period is
satisfi ed. Press to view the next screen.
When the battery voltage falls below the refl oat
set point, a fl oat cycle recharging starts. This can
act as a maintenance recharging or a recharging
when intermittent DC loads are running and an
AC source is available for recharging. This setting
ranges between 12.0VDC and 13.0VDC. Press
to view the next CHARGER screen.
INC
DEC
DOWN
DOWN
DOWN
DOWN