Other Rail Voltage

The voltage of the Other Rail, which connects the PMF/IOMF CRU to
the other power supply in the enclosure (to provide power in the event of
a problem with the Main Rail power supply).

Storage ASIC

Initialization State

The status of the storage ASIC in the CRU.

Values: Initialized, Uninitialized, Unknown

Actions

Disable ServerNet Port

Disables the specified ServerNet port on this CRU. Perform this action only as directed by OSM
alarm repair actions.

Parameter: Port Number

Enable ServerNet Port

Enables the specified ServerNet port on this CRU. Perform this action only as directed by OSM
alarm repair actions.

Parameter: Port Number

Force Power Off

Use this action to power off the CRU and all of its subcomponents only if the Prepare to Power Off
or Power Off actions fail. The Force Power Off does not perform the other precautionary checks that
are done by the Prepare to Power Off and Power Off actions. However, these steps are taken:

If the SP on this PMF CRU is designated as Active (Primary), resets the SP so the peer SP
becomes primary instead

Disables the battery

Halts the processor on this PMF CRU

Power Off

Upon successful completion of the Prepare to Power Off action, you can use the Power Off action to
turn off power to the PMF2 CRU and all components. The Power Off action first performs
precautionary checks to ensure that you can safely power off the CRU. These checks ensure:

The other PMF2 CRU in this enclosure exists and is powered on.

The status of the power supply on the other PMF2 CRU in this enclosure is OK.

The other PMF2 CRU in this enclosure has ServerNet accessibility.