beautypg.com

Table 3, Table 4 – HP StorageWorks 2405 Disk System User Manual

Page 33

background image

Installation

33

In

st

al

la

ti

o

n

nominal power and redundant PDU/PDRUs. For nonredundant configurations,
divide the number of recommended PDU/PDRUs by 2.

Table 3.

Recommended PDU/PDRUs for Multiple Disk Systems in HP Legacy

Racks

No. of Disk

Systems

1.1 meter

(21 U)

1.6 meter

(32 U)

2.0 meter

(41 U)

1 – 5

2 3-foot/16-amp PDUs
or
2 19-inch/16-amp PDUs

2 5-foot/16-amp PDUs

1

or
2 19-inch/16-amp PDUs

1.Supports cabinet on/off switch.

6 – 8

NA

2

2.Rack height does not allow additional disk systems.

4 19-inch/16-amp PDRUs
or
4 19-inch/30-amp PDRUs

9 – 10

NA

2

NA

2

4 19-inch/
30-amp PDRUs

Table 4.

Recommended PDU/PDRUs for Multiple Disk Systems in HP System/

E Racks

No. of Disk

Systems

1.25 meter

(25 U)

1.6 meter

(33 U)

2.0 meter

(41 U)

1 – 4

2 19-inch/16-amp PDUs
or
2 19-inch/30-amp PDRUs

1

1.Supports cabinet on/off switch.

5 – 8

NA

2

2.Rack height does not allow additional disk systems.

2 19-inch/30-amp PDRUs

1

4 19-inch/30-amp PDRUs

9 – 11

NA

2

NA

2

4 19-inch/
30-amp PDRUs

12-13

NA

2

NA

2

4 19-inch/
30-amp PDRUs