7 the actual value 1 (iw1), 8 actual value 2 and actual value 3 (iw2/3) – NORD Drivesystems BU0080 User Manual
Page 35

6 Data transmission
35
6.4.7
The actual value 1 (IW1)
The actual value 1, i.e. the actual output frequency of the inverter, is transferred as a 16 Bit value as standard
in the actual value 1. The actual value 1 is transferred to the master in the inverter response telegram as the
second word in the process data area.
PZD1 PZD2 PZD3 PZD4
ZSW
IW1
IW2/3
IW3/2
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
The actual value 1 is transferred as a whole number in the range (-32768 to 32767). In addition to the actual
frequency, other actual inverter values can be transferred. The setting is made in P543 'Actual value 1
function'.
The settings ‘Actual frequency’, ‘Actual speed’, ‘Current’ and ‘Torque current’ are transferred as percentages of
the respective nominal values. The value 16384 (4000 HEX) corresponds to 100%. The value C000 HEX
corresponds to -100%. Actual values in the range –200% to +200% can be transferred.
With the setting ‘Digital I/O status’, the states of the control terminals and the relay (MFR) /digital outputs can
be transferred:
SK 700E/750E
Bit
Status
Bits 0-5
Digital input 1-6
Bit 6-11 for posicon special extension unit
Digital input 7-12
Bit 6 for encoder special extension unit
Digital input 7
Bits 12-15
Multifunctional relay 1-4
SK 500E
Bit
Status
Bits 0-4
Digital input 1-5
Bit 5-6 (above SK 520E)
Digital input 6-7
Bits 12-15
Relay and digital outputs 1 - 4
With the setting 'Actual position' and 'Setpoint position' the actual absolute position is transferred. The
resolution is 1 = 0.001 revolutions.
If with SK 700E/750E the value 'Setpoint position 32 Bit' is set in parameter P546 (Setpoint function 1), then
the actual value (setpoint or actual position) is also transferred as a 32 Bit value in PZD2 and PZD3:
PZD1 PZD2 PZD3 PZD4
ZSW
IW1
IW2
6.4.8
Actual value 2 and actual value 3 (IW2/3)
It is possible to forward two more actual values to the controller if PPO type 2 or 4 is used for transfer.
The assignment of the actual values 2 and 3 to the process data words PZD3 and PZD4 is carried out in the
same way as the assignment of setpoints 2 and 3. These also differ in sequence between the SK 500E and
other inverter series.