NORD Drivesystems BU0080 User Manual
Page 22

NORDAC DeviceNet Manual
22
BU
0080
GB
Parameter
Setting value / Description / Note
Comments
P546 (P)
Bus setpoint 1
In this parameter, a function is assigned to the delivered setpoint 1 (SW1) for bus control.
NOTE: Further details can be found in the respective FI manual or in the description of P400.
0 ... 7 (47)
[ 1 ]
SK 300E, SK 700E SK 750E
0 = Off
1 = Setpoint frequency (16 bit)
2 = 16 Bit setpoint position (only
posicon, SK700/750E)
3 = 32 Bit setpoint position (only
posicon, SK700/750E and if
PPO- type 2 or 4 are
selected)
4 = Control terminals posicon
(only posicon, SK700/750E,
16Bit)
5 = Setpoint position (16 Bit)
increment
1
(onlyposicon,
SK700/750E)
6 = Setpoint position (32 Bit)
increment
1
(onlyposicon,
SK700/750E)
7 = Bus IO In Bits 0-7
SK 500E
0 = Off
1 = Setpoint frequency (16 bit)
2 = Torque current limit (P112)
3 = Actual frequency PID
4 = Frequency addition
5 = Frequency subtraction
6 = Current limit (P536)
7 = Maximum frequency (P105)
8 = Actual PID frequency limited
9 = Actual PID frequency monitored
10 = Torque servo mode (P300)
11 = Lead torque (P214)
12 = Reserved
13 = Multiplication
14 = PI process controller actual value
15 = PI process controller setpoint
16 = PI process controller lead
17 = Digital In bits 0...7
18 = Reserved
19 = Set relay (P434/441/450/455=38)
20 = Set analog output (P418=31)
21 = Setpoint position Low word (SK 530E and above)
22 = Setpoint position High word (SK 530E and above)
23 = Setpoint position increment Low word (SK 530E and above)
24 = Setpoint position increment High word (SK 530E and above)
25 = ... 45 Reserved
46 = Setpoint torque process controller
47 = Gearing transfer factor
P547 (P)
Bus setpoint 2
In this parameter, a function is assigned to the delivered setpoint 2 (SW2) for bus control.
0 ... 46 (47)
[ 0 ]
0 = Off
1 = Setpoint frequency
2 = Torque current limit (P112)
3 = Actual frequency PID
4 = Frequency addition
5 = Frequency subtraction
6 = Current limit (not SK 300E)
7 = Maximum frequency (not SK 300E)
8 = Actual PID frequency limited
9 = Actual PID frequency monitored
10 = Torque (not SK 300E)
11 = Torque lead (not SK 300E)
12 = Control terminals posicon (not
SK 300E)
13 = Multiplication (not SK 300E)
14 = PI process controller actual value
15 = PI process controller setpoint
16 = PI process controller lead
17 = Digital In bits 0...7
18 = Curve travel calculator (not SK 300E)
19 = Set relay
20 = Set analog output
21 = Setpoint position Low word (SK 530E and above)
22 = Setpoint position High word (SK 530E and above)
23 = Setpoint position increment Low word (SK 530E
and above)
24 = Setpoint position increment High word (SK 530E
and above)
25 = ... 45 Reserved
46 = Setpoint, torque process controller
(not SK 300E)
47 = Gearing transfer factor (only SK 500E)
P548 (P)
Bus setpoint 3
In this parameter, a function is assigned to the delivered setpoint 3 (SW3) for bus control. This is
only available if P546
≠
is 3 (only applies for SK 700E / SK 750E).
0 ... 46 (47)
[ 0 ]
For setting values, see parameter (P547)
P551 Drive
profile
always visible
0 ... 1 (On / Off)
[ 0 = Off ]
Depending on the option, this parameter is used to activate the CANopen profile DS401
or the InterBus Drivecom profile .