6 Data transmission
29
6.4.3
Control word (STW)
.4.3
Control word (STW)
The control word (STW) is the first word transferred to the frequency inverter in the process data area in an
order telegram. For example, a control word "Ready for switch-on" corresponds to 047E
(hex)
.
The control word (STW) is the first word transferred to the frequency inverter in the process data area in an
order telegram. For example, a control word "Ready for switch-on" corresponds to 047E
(hex)
.
PZD1
PZD1 PZD2
PZD2 PZD3
PZD3 PZD4
PZD4
STW SW1 SW2/3
SW2/3
15 14
13 12 11 10
9
8
7
6
5
4
3
2
1
0
Bit
Value
Significance
Comments
0
0
OFF 1
Reverse with the brake ramp, with disconnection from supply at f=0Hz
1
ON
Ready for operation
1 0
OFF
2
Cut off voltage; the inverter output voltage is switched off; the FI enters a state
where switching on is disabled.
1 Operating
condition
OFF 2 is cancelled
2 0
OFF
3
Quick stop with programmed quick stop time; with disconnection from supply at
f=0Hz; the FI switches to starting disabled condition.
1 Operating
condition
OFF 3 is cancelled
3 0
Disable
operation
Cut off voltage; the inverter output voltage is switched off; the FI enters a state
where switching on is enabled.
1
Enable operation
The output voltage is enabled; ramp to the existing setpoint
4
0
Lock ramp generator
Ramp generator is set to zero; no disconnection from supply at f=0Hz; FI
remains in the operation enabled state.
1 Operating
condition Enable ramp generator
5
0
Stop ramp generator
The setpoint currently provided by the ramp generator is "frozen" (frequency is
maintained).
1
Enable ramp generator
Enable setpoint on ramp generator
6
0
Disable setpoint
Selected setpoint value is set to zero on the ramp generator.
1
Enable setpoint
Selected ramp generator setpoint is activated.
7 0
No
acknowledgement With the switch from 0 to 1, errors which are no longer active are
acknowledged.
1 Acknowledge
Note: When a digital input has been programmed for the "ack.fault" function,
this bit must not permanently be set to 1 via the bus (otherwise, edge
evaluation would be prevented).
8 0
1
Bit 8 active
Bus bit 8 from the control word is set. (Only for SK 200E and SK 500E)
For further details of the function please refer to parameter (P480).
9 0
1
Bit 9 active
Bus bit 9 from the control word is set. (Only for SK 200E and SK 500E)
For further details of the function please refer to parameter (P480).
10
0
PZD invalid
The transmitted process data is invalid.
1
PZD valid
Valid process data is transferred from the master.
Note:If setpoints only are transferred via the bus, this bit must be set so that
the transferred setpoint is valid.
11 0
1 Rotational
direction:
right
Rotational direction right (priority) – ON*
12 0
1 Rotational
direction:
left
Rotational direction left – ON*
13 0/1
Reserved
14 0/1 Bit 0 to switch parameter
set
15 0/1 Bit 1 to switch parameter
set
00 = Parameter set 1
01 = Parameter set 2
10 = Parameter set 3
11 = Parameter set 4
* If Bit 12=0, then "Direction of rotation right ON" applies